project on advanced monitoring system for gis substation
CHAPTER 1
INTRODUCTION
1.1
OBJECTIVE OF PROJECT
G.I.S
substations are preferred in cosmopolitan cities, industrial townships etc
where cost of land is very high and cost of G.I.S is justified by saving due to
reduction in floor area requirements. In these substations, sulphur
hexafluoride (SF6) gas is used in switchgear as insulating and arc quenching
media. Various components like circuit breakers, busbars, disconnectors,
current transformers, voltage transformers, earthing switches etc. are housed
in metal modules filled with SF6 gas.
As the dielectric strength of SF6 gas is
higher than air, the overall size of each equipment and the complete substation
is reduced to about 10% of conventional air insulated substations. When a
typical 220KV substation of 5 breaker ring bus arrangement occupies an overall
area of 100m*40m, the GIS for the same arrangement will require only 24m*9m
area. To reduction in site are will be by 19/20 of the conventional substation.
Volume wise it is only 1/60 of the conventional substations. The various
modules are factory assembled are filled with SF6 gas. Such substations are
compact and can be installed conveniently on any floor of a multistoried
building or in underground substations. All the main elements of the substation
area are completely enclosed in SF6 installation, which include circuit
breakers, loadbreak switches, isolators, earth switches, current transformers,
potential transformers, busbars, coupling capacitors and SF6 lead out bushing
insulators for connection to overhead lines, transformers or other external
equipments. Equipments such as transformers, shunt reactors, shunt capacitors,
carrier communication, line traps etc. are not part of the SF6 insulated
system.
During the last 35 years many GIS have
been installed and successfully operated worldwide. In India the first G.I.S
was installed in Mumbai more than 15 years ago and now a large numbers of units
are either in operation or in the process of being commissioned. Now G.I.S
substations are available from voltage ranges, 72.5KV to 1100KV in all types of
busbar arrangements. In Kerala, at Thiruvanthapuram two GIS substations are
installed and are under working conditions at Power house and LA complex.
From the load study
conducted in Kollam city, we can see that, the present load is 43MVA and the
load rises by about 6% annually. Moreover the number of power interruptions can
be reduced to a great extent if we set up a G.I.S substation in Kollam city. With the existing system voltage
drop is also very high which can be minimized if the proposed system is set up.
Unlike a conventional substation which needs acres of land; and that too in the
heart part of the city which is almost impossible in the current situation, a
G.I.S substation which occupies only 10% space compared to a conventional
substation is adequate. Hence the objective is to design a 110KV substation in the powerhouse compound of Kollam city
with an advanced control room.
Kollam city is a
Municipal Corporation in Kollam district in the Indian state of Kerala. It lies
71 Km north of the state capital Thiruvanathapuram. It is also the headquarters
of the Kollam District, one among the 14 districts in the state of Kerala. It is
bound on south by Thiruvanathapuram district, on the north by Pathanamthitta
and Alappuzha, on the east by Tamil Nadu and on the west by the Arabian Sea.
The town is very famous for cashew processing and coir manufacturing. It is the
southern gateway to the backwaters of Kerala, and thus, a prominent tourist
destination.
The geographical coordinates for Kollam
are 9.28’45° N 76.28’0° E. The district covers an area of 2,492 km² and ranks
seventh in the State with respect to area. Kollam like other districts in the
state is moderately industrialized. Some of the major employers in the public
sector are Indian Rare Earth (IRE), Kerala Metals and Minerals Limited at
Chavara; United Electrical Industries (popularly known as the Meter Company)
and Parvathi Spinning Mills at Kollam. Cashew processing and coir production
are the two most important sources of employment.
MAP
OF KOLLAM CITY
1.2
SWITCH GEAR COMPONENTS OF A SUBSTATION
During the operation of the power system
the generating plants, transmission lines, distributors and other electrical
equipments are required to be switched on or off under both normal and abnormal
operating conditions. The apparatus including its associated auxiliaries
employed for controlling, regulating or switching on or off the electrical
circuits in the electrical power system is known as switch gear.
With the advancement of electrical power
systems, the lines and other equipment operate at very high voltage and carry
large current. Whenever a short-circuit occurs, a heavy current flows through
the equipment causing considerable damage to the equipment and interruption of
service, so in order to protect the lines, generators, transformers and other
electrical equipment from damage automatic protective device or switchgear is
required.
1.2.1 SWITCHES
A switch is used in an electric circuit
as a device for making or breaking the electric circuit in a convenient way
i.e. by the simple motion of a knob or handle to connect together or disconnect
two terminals to which wires or cables are connected. The switches may be
classified into
a) Air
switches
i)Air-break switches
ii)Oil switches
b) Oil
switch
As their names imply, air switches are
those whose contacts are opened in air, while oil switches are those whose
contacts are opened under oil. Oil switches are usually employed in very high
voltage heavy current circuits. Air switches are further classified as
air-break switches and isolators (or disconnector switches).
i) AIR-BREAK SWITCHES:
The air break switch has both the blade
and the contact equipped with arcing horns. Arcing horns are piece of metal
between which the arc resulting from opening a circuit carrying current is
allowed to form. As the switch opens, these horns are spread father apart and
the arc is lengthened until it finally breaks.
Air-break switches are of several
designs. Some are operated from the ground by a hook on the end of a long
insulated stick: some others through a system of linkage are opened by a crank
at the foot of the pole. Where more than one conductor is opened, there may be
several switches mounted on the same pole. These may be opened singly or
altogether in a “gang” as this system is called. Some switches are mounted so
that the blade opens download and these may be provided with latches to keep
the knife blade from jarring open.
ii)ISOLATORS:
Isolators (or disconnect switches) are
not equipped with arc quenching device and therefore not used to open circuits
carrying current. As the isolator isolates one portion of the circuit from
another and is not intended to be opened while current is flowing. Isolators
must be opened until the circuit is interrupted be some other means. If an
isolator is opened carelessly, when carrying a heavy current, the resulting arc
could easily cause a flash over to earth. This may shatter the supporting
insulators and may even cause a fatal accident to the operator, particularly in
high voltage circuits. While closing a circuit, the isolators is closed first,
then circuit breaker. Isolators are necessary on supply side of circuit
breakers in order to ensure isolation (disconnection) of the circuit breaker
from the lie parts for the purpose of maintenance.
1.2.2 PROTECTIVE
EQUIPMENT
Protective equipment is an extremely
important item in system design it is installed to function under abnormal conditions to prevent
failure or isolate trouble and limit its effect. It must function reliably and
quickly. It should be selected for greatest reliability, speed of operation,
and simplicity and should be consistent with the system design.
1.2.2.1 CIRCUIT
BREAKERS
A circuit breaker is a
mechanical device designed to close or open contact members, thus closing or
opening an electrical circuit under normal or abnormal conditions. It is so
designed that it can be operated manually (or by remote control) under normal
conditions and automatically under fault conditions. An automatic circuit
breaker is equipped with a trip coil connected to a relay or other means, designed
to open or break is closed, considerable energy is stored in the springs. The
contacts are held together by means of toggles. To open the circuit breaker,
only a small pressure is required to be applied on a trigger. When the trigger
is actuated by the protective relay, it trips and the potential energy of the
springs is released and the contacts open in a fraction of seconds.
A
circuit breaker must carry normal load currents without over heating or damage
and must quickly open short-circuit currents without serious damage to itself
and with a minimum burning of contacts. Circuit breakers are rated in maximum
voltage, maximum continuous current carrying capacity, maximum interrupting
capacity and maximum momentary and 4 second current carrying capacity.
The breakers are provided with operating
mechanisms which are in turn, actuated by power supplied through suitable
relays. In indoor substations, breakers of high rupturing capacities are
enclosed in fire-proof compartments. Lift-up or draw out type breakers which
incorporate a disconnect feature on each side are the most common in design and
applications. Air circuit breakers are often employed instead upto 15KV in
these units and oil recloser is sometimes employed to cut down the cost in small
rural substations.
Thus
the functions of a circuit breaker are
·
To carry full-load current continuously.
·
To open and close the circuit on load.
·
To make and break the normal operating
current.
·
To make and break the short-circuit
current of magnitude upto which it is designed for.
1.2.2.2 PROTECTIVE
RELAYS
The
protective relay is an electrical device interposed between the main circuit
and the circuit breaker in such a manner that any abnormality in the circuit
acts on the relay, which in turn, if the abnormality is if a dangerous
character, causes the breaker to open and so it isolate the faulty element. The
protective relay ensure the safety of the circuit equipment from any damages
which might otherwise caused by the fault.
1.
Sensing
element, sometimes also called the measuring elements,
responds to the change in the actuating quantity, the current in a protected
system in case of over-current relay.
2.
Comparing
element sieves to compare the action of the actuating
quantity on the relay with a pre-selected relay setting.
3.
Control
element on a pick of the relay, accomplishes a sudden change
in the control quantity such as closing of the operative current circuit.
1.2.2.3 CURRENT
TRANSFORMERS (CT’s)
These instrument transformers are
connected in newer circuits to feed the current coils of indicating and
metering instrument (ammeter, wattmeter and watt-hour meters) and protective
relays. Thus the CT’s broaden the limits of measurements and maintain a watch
over the currents flowing in the circuit and over the power loads. In high voltage
installations CT’s in addition to above also isolate the metering instruments
from high voltage.
The current transformers basically
consist of an iron-core on which are wound a primary and one or two secondary
windings. The primary is directly inserted in the power circuit (the circuit in
which current is to be measured) and to the secondary winding or windings the
indicating and metering instruments and relays are connected. When the rated
current of CT flows through its primary winding a current of 5 ampere will
appear in its secondary winding. The primary winding is usually single turn
winding and the number of turns on secondary winding depends upon the power circuit
current to be measured. The larger current to be measured more the numbers of
turns on secondary. The ratio of primary current to the secondary current is
known as transformation ratio of CT.
The current transformers are rated for
rated voltage of the installation, the rated currents of the primary and
secondary windings and the accuracy class. The accuracy class indicates the
limit of the error in percentage of the rated turns ratio of the given current
transformer. Current transformers are available in the accuracy classes 0.5, 1,
3 and 10.
1.2.2.4 POTENTIAL
TRANSFORMERS (PT’s)
The potential
transformers are employed for voltages above 380 volts to feed the potential
coils of indicating and metering instruments (voltmeters, wattmeters, watt-hour
meters) and relays. The transformers make the ordinary low voltage instruments
suitable for measurement of high voltage and isolate them from high voltage.
The primary winding of the potential transformer is connected to the main
bus-bars of the switchgear installation and to the secondary winding, various
indicating and metering instruments and relays are connected.
When the rated high voltage is applied to
the primary of a PT, the voltage of 110volts appears across the secondary
winding. The ratio of the rated primary voltage to the rated secondary voltage
is known as turns transformation ratio. The potential transformers are rated
secondary are rated for primary and secondary rated voltage accuracy class,
number of phases and system of cooling.
1.2.2.5 LIGHTNING
ARRESTERS
The lightning arrester
is a surge diverter and is used for the protection of power system against the
high voltage surges. It is connected between the line and earth and so diverts
the incoming high voltage wave to the earth. Lightning arresters act as safely
valves designed to discharge electric surge resulting from lightning strokes,
switching or other disturbances, which would otherwise flashover insulators or
puncture insulation, resulting in a line outage and possible failure of
equipment. They are designed to absorb enough transient energy to prevent
dangerous reflections and to cut off the flow of power frequency follow (or
dynamic) current at the first current zero after the discharge of the
transient. They include one or more sets of gaps to establish the breakdown
voltage, aid in interrupting the power follow current, and prevent any flow of
current under normal conditions (except that step shunting resistors, when used
to assure equal distribution of voltage across the gaps permits a very small
leakage current). Either resistance (valve) elements to limit the power follow
current to values the gaps can interrupt, or an additional arc extinguishing
chamber to interrupt the power follow current are connected in series with
gaps. Arresters have a short time lag of breakdown compared with the insulation
of apparatus the breakdown voltage being nearly independent of the steepness of
the wave front.
Transmission
line is protected from direct strokes by running a conductor known as
ground wire, over the towers or poles and earthed at regular intervals
preferably at every pole/tower.
Substations,
interconnectors and power houses
are protected from direct strokes by earthing screen that consists of a network
of copper conductors, earthed atleast on two points, overall the electrical
equipment in the substation. The ground wire or earthing screen does not
provide protection against the high voltage waves reaching the terminal
equipment, so some protective devices are necessary to provide protection to
power stations, substations and transmission lines against the voltage wave
reaching there. The most common device used for the protection of the power
system against the high voltage surge is surge diverter which is connected
between line and earth and so diverts the incoming high voltage wave to earth.
Such a diverter is also called the lighting arrester.
Different
types of gaps and lightning arresters (rod gap, horn gap, electrolytic
arrester, oxide film arrester, thyrite arrester, expulsion type lightning
arrester, valve type lightning arrester) etc.
1.2.2.6
EARTHING OF POWER SYSTEM
The term ‘earthing’ means connecting of
non-current carrying part of the electrical equipment or the neutral point of
the supply system to the general mass of earth in such a manner that at all
times an immediate discharge of electrical energy takes place without danger. The earthing is provided with the following
objective.
·
For the safety of equipment and
personnel lighting and voltage surges providing the discharge path for
lightning arresters, gaps and similar devices.
·
For providing ground connections for
ground neutral systems.
·
For providing a means of positively
discharging and de-energizing feeders or equipment before proceeding with
maintenance on them.
·
For safety of personnel from the
electric shock ensuring that non-current carrying parts, such as equipment
frames are always safely at ground potential even though insulation fails.
Grounding of power systems is highly
important. A substantial and adequate ground that will not burn off or permit
dangerous rise in voltage under abnormal conditions is essential. Extensive
damage and dangerous conditions have arisen when inadequate grounds have been
provided. Multiple ground and multiple connections to them are usually
desirable to ensure ground protections, even though one ground or connection
opens owing to burn-off or other conditions such as high resistance. The
station earthing system should have low resistance. The station earthing system
should have low resistance.
The earthing can be divided into neutral
and equipment earthing .Neutral earthing (or grounding) deals with the earthing
of the system neutral to ensure system security and protection. Neutral earthing
is also called the system earthing. Equipment earthing or safety earthing deals
with earthing of non- current carrying parts
of the equipment ensures safety of potential and protection against
lightning. Equipment earthing also helps in earth fault protection. The earthed
parts remain at approximately earth potential even during flow of fault
current.
In neutral earthing, the points (star
point) of star connected 3-phase winding of power transformers, generators,
motors, earthing transformers are connected to low resistance ground. The chief
advantage s of neutral earthing are:
·
Persistence arching ground can be
eliminated by employing suitable protective gear.
·
Earth fault can be utilized to operate
protective relays to isolate the fault.
·
The voltage of healthy phases remains
nearly constant.
·
Induced static charges are conducted to
earth without disturbance.
·
There is a possibility of installing
discriminative protective gears on such systems.
·
This system gives reliable service and
greater safety to personnel’s and equipment.
·
Maintenance and operating cost of such
systems over isolated system is comparably less.
1.2.2.7 CONTROL ROOMS
The control room (or the remaining room)
is the nerve center of a power station. The various controls preferred from
here are voltage adjustment load control, emergency tripping of turbines etc. and
the equipment and instruments housed in a control room are synchronizing equipment
isolators, relays, ammeter and watt meters, KWh meters.
The location of control room in relation
to other sections of the power station is also very important. It should be
located away from the source of noise and should be near the switch house so as
to save multi-core cables used for interconnection of course, if there is any
fire in switch house, the control room should remain unaffected. Also here
should be access from the control room to the turbine house. The control room
should be neat and clean, well-ventilated, well lighted and free from droughts.
There should be no glare and the colour scheme should be soothing to eyes. The
instrument should have scales clearly marked and properly calibrated and all
the apparatus and circuit should be labeled so that they are clearly visible.
* *
* * *
CHAPTER 2
STUDY OF GIS SUBSTATION
2.1INTRODUCTION
Substations
where gas is used in the switchgear as switching medium, insulating medium and
as arc quenching medium are called G.I.S. substation. SF6 gas is used for this
purpose due to its chemical and thermal characteristics.
2.2MAIN
FEATURES
·
Single phase enclosed design.
·
Small dimensions allowing economical
space saving.
·
Indoor and outdoor applications.
·
High reliability in service, independent
of ambient influences.
·
Flexibility and optimal arrangement of
equipment, assured by highly modular element system.
·
Light weight, gas tight aluminum
enclosures with low electrical losses and corrosion resistance.
·
Earthed enclosures assuring maximal
protection against electrical shock for the operating personnel.
·
Low maintenance and long service life.
·
Environmental friendly behavior.
·
Epoxy resin barrier and support
insulators.
·
Circuit breaker on single pressure
principle actuated by hydraulic drive.
·
Protection against dangerous
overpressure through bursting membranes.
·
Quick site assembly assured by infactory
preassembled bays shipping units.
·
Compliance with international
standards-IEC 517. IEC 694 etc.
2.3ADVANTAGES
OF G.I.S OVER CONVENTIONAL TYPE
1.
Lesser
Area
For
conventional type of substations the yard equipment itself occupies a comparatively
larger area say 40×40m approximately. This is in addition to the area required
for the construction of the control room. It is estimated that the area
required for the construction of 66KV substation including the control room is
about 3.5 acres. But the area required for G.I.S substation is only less than
1/10th of this, i.e. approximately 30 cents, as the equipments are
enclosed in a metallic chamber and installed in control room itself.
In
bigger cities where space constraints pose a great problem the preference of
G.I.S substation to conventional substations is justified.
2.
Easy
Maintenance
The fully metal enclosed principle adopted
for the switchgears guarantees that no outside influence can, affect the
insulating materials used in the assembly. Periodic maintenance such as
cleaning the insulator, protection against corrosion etc, nominally applicable
to conventional yard equipments are not necessary in G.I.S substations.
Maintenance activities such as greasing, checking the driving mechanism of
circuit breaker contacts, SF6 gas monitoring etc are very easy.
3.
Remote
and Supervisory Control Facility
Even though remote and supervisory control
facility can be provided equally for air insulated substations also, the
functioning of the various equipments are not fool proof. In the, since the
operation will be trouble free.
4.
Future
Expansion
The expansion of G.I.S substation can be
done within a short period compared with other types, if the expansion is
foreseen at the time of construction by adding more additional bays
5.
Phenomena
of Corona Discharge
The corona discharge is a regular
phenomenon for voltages above 110KV for outdoor construction. In a thickly
populated area, this is quiet undesirable.
6.
General
Since no structure is visible outside and
even the transformers are kept indoors.
GIS substations will only add to the aesthetic beauty of the area.
Salinity poses a serious threat especially
to those substations which have proximity to the sea. Equipment structures get
corroded due to salinity. This problem does not arise in the case of GIS
substations as the yard equipments are enclosed. GIS station does not cause any
pollution problem and even the humming of transformers is not audible outside,
as the transformers are kept indoors.
2.4
SF6 GAS THEORY
SF6 gas is used in G.I switchgear as an
insulating medium and as a switching gas due to its dielectric and arc
quenching properties. The gas is produced by direct reaction at 300 degree
centigrade between molten sulphur and fluorine gas, generated by electrolysis
of hydrofluoric acid HF. It is chemically stable, non- toxic and incompressible.
If SF6 is used at pressures which ensures that no liquefaction occurs, the
problem with consideration droplets etc are also avoided.
2.4.1 SF6 AS AN INSULATING
MEDIUM
Insulation
by SF6 gas reduces the insulating distance i.e., the distance between the phases
and two adjacent bays, thereby reducing the space required for a substation.
The
gas is electronegative in character, that is, an atom or molecule of SF6 will
attract and hold the electrons. The electronegative gases are good dielectrics.
From the graph above,
the following observations can be made. Electric strength at 20 degree
centigrade
SF6
1 bar 20 degree
centigrade - 75KV/cm
6bar 20 degrees
centigrade - 375Kv/cm
AIR
1 bar 20 degree
centigrade - 30KV/cm
6 bar 20 degree
centigrade - 150Kv/cm
The
above figures show that the withstand voltage of SF6 is 2.5 times higher than
that of air under the same temperature and pressure. In other words, to meet
the same voltage requirements SF6 requires an enclosure of lesser volume and
weight than that required for air.
In the case of internal fault the arc
developed in SF6 has lower arc voltage than the arc in compressed air. This
results in lower pressure increase in SF6 than in compressed air. The G.I
switch gear is so designed that this pressure increase can be accommodated in
the circuit breaker with less difficulty. Due to large density of sf6 the
thermal conductivity is also high, the ratio for the same SF6/air is 2.5:1.
Hence the dissipation of the generated heat by the ohmic resistance of the
conductors via. The enclosure is more in case if SF6 than that of air. But is
rather expensive and hence its leakage percentage has to reduced has to reduced
to minimum. A standard allowance for this is 1% per annum.
2.4.2
SF6 AS A SWITCHING GAS
SF6
is also used as arc-extinguishing medium in circuit breakers of the G.I.S.
Circuit breaker is the most important safety element in a power supply system.
The C.B must be capable of interrupting large currents at high electro motive
force.
The only element that can change quickly
from conductive to non-conductive condition is the electric arc. The C.B
interrupts the current by the cooling of the electric arc .developed between
the contacts after they have been opened. When the current wave passes through
zero, the energy supplied to the arc equals zero and if there is sufficient
cooling, current will be interrupted. After current interruption the transient
recovery voltage will be applied to the gas column which is still hot. If the
arc quenching medium has not regained its electric strength at this time, there
is a possibility restriking of the arc.
In SF6 circuit breaker, during the arcing
period, SF6 gas is blown axially alone the arc. The gas removes the heat and
reduces arc diameter during the decreasing mode of the current wave. The
diameter becomes small during current zero and the arc is extinguished. Due to
excellent property of SF6 gas maximum values it regains its dielectric
properties after the final current zero and prevent the arc from restriking.
The arc-time constant, which is the time required for a medium to regain its
dielectric strength after final current zero, for SF6 as is of the order of a
few micro seconds.
When
switching to a short-line fault, the rate of rise of recovery voltage is so
large that it is almost impossible to quench the arc with compressed air, and
is difficult with oil. But with SF6 this is very simple due to its large
arc-quenching capacity.
In addition, SF6 has a good thermal
conductivity in the temperature range of 2000-3000 degree Kelvin. Due to this
high thermal conductivity, heat exchange between the hot ionized core and
surrounding medium is very fast, which assists in excellent arc quenching.
2.4.3 GAS QUALITY
The gas applied in switchgear should be
clean without any pollutants. If the gas becomes heavily polluted through
internal fault it should not be used any longer and refilling should be carried
out. The gas for filling or replenishing is called the clean gas in operation
is called operating gas.
2.5 ARRANGEMENT OF THE
INSTALLATION
In
a G.I.S substation the EHT side is protected by gas insulated switchgear filled
with SF6 gas. Switchgear suitable for operation up to 525KV has been developed,
this switchgear features a compact and convenient layout, safety precaution for
service personnel and high operational reliability. In general switchgear
provides perfect system security under specified operating conditions. The switchgear
is made up of different compartments in which all operating units in a three
phase construction are contained. The compartments are-
1) Circuit
breaker compartment
2) Bus
bar compartment and
3) Cable
termination compartment
These compartments are interconnected by means of
disconnectors.
2.5.1
CIRCUIT BREAKER COMPARTMENT
This compartment consists of a three
phase conductor system. The fixed contact of the disconnections is mounted on
this conductor system. From the conductor system conductive connection go via
laminated contacts to the moving contacts of the three circuit breaker
elements. From the holders of the fixed contact, the conductors for each phase
are connected to a three phase conductor system. This connection is done via a
current transformer. On this are located the knife shaped fixed contacts from
the disconnected to the cable termination compartment. But in the case of a
coupling panel, connection to this cable termination compartment is not
applicable since these contacts apply to the disconnected of the second bus bar
system. The circuit breaker in this condition is situated between the two bus
bar disconnections. The three singe phase circuit breaker interrupters are
driven by a hydraulic system mounted on the front of circuit breaker
compartment.
A cylindrical insulator is situated in
the cable termination compartment. The knife shaped fixed contact from the
disconnector are mounted on it. A three phase earthing switch is mounted on the
upper wall of the cable termination compartment. Current transformer as are
places per phase in the circuit breaker compartment between the circuit breaker
and the cable or the transformer disconnector.
2.5.1.1 INTERRUPTER
Interrupter is the active component
in the circuit breaker. An insulation
cylinder is spitted between the flinch and the contact holder inside the
contact holder a fixed piston is mounted on a tube with flow orifice. The
laminated sliding contacts ensure that the current is conducted form the
connection to the bus bar system via the contact holder housing to the copper
shaft and the nominal and arcing contacts which are connected to it. The fixed
part of the nominal and the arcing contacts are mounted in the second contact
holder in which filler with molecular sieve is also located. The second contact
holder is connected with the first by means of an insulation cylinder.
2.5.1.2 INTERRUPTER
FUNCTIONING
Opening:
During the opening of the interrupter the
gas is being compressed between the piston and movable cylinder. After the
opening of the nominal current contacts and the arcing contacts, arcing will
occur over the latter. This arc heats the gas locally to some thousands of
Kelvins. As long as arcing continues, the accompanying pressure increase will
prevent the compressed gas in the cylinder from escaping. At the moment of the
first occurrence of current zero the arc is extinguished and the gas escapes
from the cylinder via gaps in the nozzle. The quality of the gas is so quickly
restored by the flow of cool and clear SF6 gas that re-ignition will not take
place and the recovery voltage us retained. The polluted gas is filtered in the
filter which holds the pollutants.
Closing:
During the closing operation of the
interrupter the sequence is reversed, in order to allow filling of the
compressor chamber with SF6, inlet valves are mounted in the non moving piston.
2.5.1.3 DRIVING
MECHANISM OF THE CIRCUIT BREAKER
The energy for opening and closing the
interrupter is provided by the driving mechanism which consists of the
mechanical part and hydraulic part. Hydraulic pump unit pressurizes and
maintains the pressure in hydraulic system including the accumulator. This pump
is driven by an electric motor. A hand pump is mounted in parallel for operating
the circuit breaker during servicing and maintenance. Supply to the electric
pump motor is 415/220V ac. When the pump units motor is activated, the oil is
sucked from the tank and compressed via non-return to the accumulator. If the
pressure of the hydraulic system goes beyond 300 bar the hydraulic safety valve
mounted in the pump unit opens and safe pressure is maintained.
The accumulator of a pressure cylinder
with two chambers separated from each other by a floating piston. One chamber is
filled with high pressure nitrogen and the other chamber which is connected to
the hydraulic system is filled with oil while the hydraulic system is being
pressurized, the piston is driven by the oil compressing the gas in the other
chamber. During a switching on and off cycle the oil is driven at a great
spread by the compressed gas in to the drive cylinder. The compressed gas thus
as a spring. The oil volume in the accumulator is sufficient for the completion
of an open-close-open cycle or to close-open cycles. The linear motion of the
drive cylinder is converted in to a linear motion of the interrupter contacts
by the mechanical part of the drive which consists of a number of levers
shafts, driving rods etc. shaft goes through a gas tight sealing in the
compartment and is connected by means of a crank to a system of 3 rods called
tumblers. These tumblers convert the rotating motion of main shaft into linear
motion of three driving rods and interrupter contacts.
2.5.2 TERMINATION COMPARTMENT
The circuit breaker is connected to high
voltage termination compartment. This
termination compartment is made with:
Cables (dry, oil filled
or gas pressure type)
Direct connections to a
transformer
Bus trucking with SF6-Air
bushing.
For high voltages DC testing this
compartment is provided with a facility that allows access to HV conductors
without evacuating the compartment or even without lowering the pressure of the
gas. This device allows test to be performed on the cable (HVDC, impulse) for
cable fault detection without necessitating the opening of the compartment or
the removal of the SF6 gas. For measuring and protection a voltage compartment
can be housed on the termination compartment.
2.5.3 BUS- BAR COMPARTMENT
The Bus bar system is mounted on the top
of the circuit breaker compartment. This is constructed from sections with the
same length as the normal panel width. The ends of the compartments are sealed
off by means of raised covers. Three phase conductor system is suspended from
trident insulators. The disconnections
knife shaped fixed contacts are situated on the conductors. There is room in
the end covers for a three phase bus bar earthing switch.
2.6
DISCONECTORS AND EARTHING SWITCH
The function of a disconnector in GI
switch gear is similar to that of an isolator in the substation yard. The
disconnector is of three phase type. The disconnector are of double gap type
and can be used for affecting isolation between-
1)
Bus bar system and circuit breaker.
2)
Cable and circuit breaker and
3)
Line and circuit breaker
The disconnectors form a single gas
barrier between the adjacent gas compartments and achieve electrical isolation
of the adjacent compartments by means of an electrical interruption of both
sides of the gas tight barrier.
As shown in the fig, in open position the
contacts are earthed. As a result an earthed barrier is created between the
adjacent compartments of the installation. Because of the safety of the working
personal is guaranteed.
2.6.1
ARRANGEMENT OF DISCONNECTORS
An insulator is located between two
compartments and maintains gas seperation fitted in one line. Three rotatable
conducting shafts pass through the insulator. In both compartments contact
holder are mounded on these shafts .We can see contact fingers fitted on these
contact holders. In the closed position these contacts are making contact with
the fixed knife on the conductors in the adjacent compartments. Insulating
shafts are fitted above the mobile contact holder. By means of the insulating
shaft, the conducting shaft together with the contact holders can be rotated
during switching through an angle of 180 degrees .In this position, the contact
fingers will make contact with the earthing contact on the wall of the
compartment. Note that the three phase conductors are situated one above the
other in the bus bar and hence the disconnector the fixed knife contacts on the
cable termination compartment are fixed in the same level .Here the three
disconnector shafts and the three drive shafts are of equal length. Disconnectors
are operated by a drive mechanism for which energy is supplied by an electric
motor working on 110VDC. Disconnectors
can be operated manually also.
The insulating shafts are connected to
the gas tight bearing bushes in a claw like connections. These bushes are
located in the aluminium drive box. Worm wheels are mounted above the bushes,
each is driven by a worm. The worm shafts are coupled and on the one side a
revolving handle can be fitted. The electric
motor with gearing is mounted on
the same side.By use of handle the safety switches interrupts the motor supply.
A system of auxiliary contacts are coupled to the worm wheel away from the
motor. The position indication is also mounted on the wheels.
2.6.2
DISCONNECTOR LOCKING DEVICE
The diconnector is
provided with an electrical/mechanical locking device. When the handle is
fitted, the supply to the motor is automatically interrupted. For assembly and
maintenance work the disconnector can be locked by attaching the locking plate.
Switching is then prevented both mechanically and electrically.
2.6.3
EARTHING SWITCH
The function of an earthing switch in
G.I.S switchgear is to earth a cable, a line or the bus bar to provide safety
for the working personnel during tests or maintenance .The earthing switch is
also used for earthing parts of the installation during tests. The earthing
switch is of three phase, fault making type, that is, it is possible to switch
on to a live conductors. The earthing switch can be operated manually or by
means of a driving motor operated at 110 VDC and spring mechanism.
Ref figure, in these three parallel
arms with double contact knives are mounted on a 90 degree rotating shaft. In
the ‘ON’ position these knives make contact with the receiving contacts on the
conductor system in the cable termination unit or bus bar. This active section
is mounted in a housing, which is mounted on the cable termination unit or bus
bar by means of a rectangular flange connection. One end of the shaft passes
through the housing to the outside where it is driven by a
motor-reducer/located-spring mechanism.
2.7
LOCAL CONTROL CUBICLE
A local control cubicle is mounted on
the front side of the switchgear foe the various operations and control of the
equipment parts. Circuit breakers, disconnectors, earthing switches etc. can be
operated from L.C.C. This is in addition
to the operation which normally takes place in the central panel in the
operator’s room. Provision for signalling alarm is also given in the Local
Control Cubicle.
For example:
·
Position indicators
·
Auxiliary contacts
·
Gas density metering
·
Hydraulic pressure metering etc
Sometimes alarms are
interfered by switching the circuit breaker.
For
example: Gas density metering. This is one of the main alarms connected inside
the L.C.C. but due to contact bouncing when a circuit breaker is closed or
opened, an alarm may be caused which is not realistic. As a protection against
this problem time delay is made in all outgoing gas density alarm signals by
adjusting the connecting relay. Contact bouncing can occur in the hydraulic oil
metering device also. Hence their contacts also have to be delayed. Since the
oil needs more time to stop oscillating, a time delay of 20 seconds is set for
the time relay to initiate the alarm. Position indication in the L.C.C. is
achieved by using special type of indication where the green indicator will
show the open position and the red indicator shows the closed position.
Components inside the L.C.C. such as contactors, micro circuit breakers, push
button etc are commonly used items only.
2.8
CURRENT TRANSFORMERS AND POTENTIAL TRANSFORMERS
2.8.1
CURRENT TRANSFORMERS
The current transformers are mounted in
the circuit breaker compartment as shown in figure. The function of CT’s are-
·
Metering
·
Line or transformer protection
·
Line or transformer back-up protection
·
Bus-bar protection
The CT’s essentially consist of primary
and secondary coil and core. The magnetic circuit in most cases is constructed
in the form of rings with cold grain oriented silicon steel or nickel alloy
according to the performance required. Each secondary coil is wound on
insulated ring core and insulated primary passes through this ring.
The
insulated primary conductors pass through the porcelain and the primary leads
are taken out through small terminal bushings fixed to the side of expansion
chamber on the upper end of the porcelain. The secondary terminals are brought
out. The terminal rings and terminal box are fixed to the tank.
Although CT’S in G.I.S. equipments look
like a very robust object, it is a valuable high quality instrument. Because
the outside of CT is not protected mechanically, the winding insulation can be
damaged easily by kicking or dropping the CT. Hence utmost care should be taken
at the time of handling of CT.
Moisture can influence the dielectric
property. Moreover aggressive chemical product may be formed from moisture and
derivatives and hence a CT is always kept dry.
2.8.2
VOLTAGE TRANSFORMERS
An inductive SF6 insulated voltage
transformer consist of three single phase transformers located in one
compartment adjacent to three cable connection compartment. The VT essentially
consists of primary and secondary windings such as core and porcelain bushing.
For the purpose of gas system, the cable connection compartment is
interconnected with the compartment for VT by a tube connector as shown in
figure.
The purpose of interconnection is the
mutual control of gas pressure in both compartments. For maintenance work in
the cable connection compartment, the value (9) is available to keep the
voltage transformer compartment under an over pressure of 0.5 bar SF6. This is
usually monitored via a pressure gauge (8) with a maximum of 2 bar between VT
and cable connection department. During operation in the substation the handle
of the valve must be removed to ensure that the valve is not closed. In that
case no control of the pressure and density of the voltage transformer
compartment is possible. For cable testing purpose the VT can be disconnected
by means of the built in isolating device (5).
The operating sequence
of this isolator is:
·
Remove the cover (A).
·
Unscrew bracket (B) from ring C and
bracket (D).
·
Remove the bracket (B).
·
Turn the bolt head E in the centre
counter-O in front.
·
Fit bracket (B) with the indication-O in
front.
·
Connect bracket (B) to the ring and
bracket.
·
For bringing into the closed position
(“I”) follow the reverse sequence.
2.9
EARTHING OF SUBSTATION
Earthing
is to be provided in AC due to the following reasons-
1. To
provide a means to carry electric currents into the earth under normal and
fault conditions, without exceeding any operating and equipment limits or
adversely affecting continuity of service.
2. To ensure that a person in the vicinity of
grounded facilities is not exposed to the danger of electric shock.
The
effect of an electric current passing through the virtual parts of a human body
depends on
1) Duration
2)
Magnitude
3) Frequency
The
following parameters have to be taken into consideration for designing earthing
for substations.
(A) RESISTANCE UNDERNEATH THE FEET
The
resistance underneath the feet is determined by the following parameters:
1.
Resistivity of the ground.
2.
Circuit (foot-foot or hand-free).
3.
Mutual resistance between foot resistances.
(B) RESISTANCE OF THE GROUND BENEATH
THE FOOT
RFOOT=Q/(4.b)
(C) MUTUAL RESISTANCE BETWEEN THE FEET
RM
FOOT
=Q/(2π*dFOOT)
With Q
: resistivity of earth [m]
b
: equivalent radius of the foot
[m]
dFOOT :
separation distance of feet [m]
(D) RESISTANCE OF THE HUMAN BODY
Extensive
tests also performed showed the following values of the resistance of the human
body:
AC
resistance from hand to hand: 2330 ohm
AC
resistance from hand to (both) feet: 1130 ohm
These
values can be increased due to insulation of shoes, dry hands etc.
NOTE
: According to IEEE Std. 80
1.
Hand and shoe contact resistances are
assumed to be zero.
2.
A value of 1000 ohm is selected for the
calculation from hand-to-hand. Hand –to-(both)-feet and foot-to-other-foot
>R
B=1000
ohms
(E) STEP VOLTAGE CIRCUIT
The
step voltage circuit is defined by a current flowing from one foot to the
other, so that the resistance underneath the feet is placed in series.
The
resistance underneath the feet R2FSis given by,
R2FS=
2(RFOOT - RM FOOT)
Approximately
this may be written as
R2FS
= 6Q, where Q= resistivity of the earth (ohm meter)
The
resistance of the accidental circuit
RA=
RB
+ R2FS
(F) TOUCH VOLTAGE CIRCUIT
This
is defined by a current flowing from both feet to the hands so that the
resistances underneath the feet placed in parallel.
The
resistance underneath the feet R2FP is given by
R2FP=
0.5 (RFOOT+
RM
FOOT)
Approximately,
R2FP=
1.5Q
The
resistance of the accidental circuit is given by,
RA=
RB+
R2FP
(G) FAULT CURRENT
The
fault current is the maximum possible current with an appreciable probability.
Fault current, IF is given below
IF=
3Io (Io is the symmetrical fault)
Where
Io= [E/3] x 1/ [Z1+Z2+Z0+3Ri] for a single line to ground fault with
E = Nominal system voltage
Z0
= Zero- sequence (subtransient) reactance.
Z1
= positive sequence (subtransient) reactance.
Z2
= Negative sequence (subtransient) reactance.
R1
= Estimated minimum resistance of the fault itself (normally 0).
Fig. Comparison of conventional substation
& GIS substation.
Fig.Over
all view of 66KV GIS substation
Fig.Hydraulic
system along with CB contact
Fig.SF6
gas filling system
Fig.Sf6
gas monitoring system
Fig.Ring
main unit
Fig.Internal
view of ring main unit
Fig.Cable
termination compartment
Fig.Top
view of GIS
2.10
HYDRAULIC PART OF THE DRIVE
2.10.1
HYDRAULIC DRIVE UNIT
A large number of components such as
magnetic valves, control valves, non-return valves, restriction of the main
cylinder etc, are integrated in the hydraulic drive unit. The piston rod of the
main cylinder is connected to the crank from the central shaft in the drive
box. The differential is constructed in a way that it will hydraulically brake
at the end of both the close and opening stroke. Restriction in the oil
channels makes it possible to adjust the required speed characteristics. There
is a single control circuit for switching on (a) and a double control circuit
(b, b1) for switching off.
Functioning:
When the magnetic valves (a,b,bl) are
energized the associated servo buster valves (c and d respectively) are opened
(“c“ is for closing and “O“ is for tripping of the circuit breaker).As a result
of this the bi-stable control valve (e) is placed in the corresponding
position. These final positions are maintained on the one hand by a mechanical
restraint and on the other by the differential action of the valve. The
bi-stable valve operates the ports of the main cylinder, in which a
differential position can move (f). Should the oil pressure drop, the circuit
breaker is locked in the ON position by locking cylinder (h).
The drive energy is given by the
hydraulic (B) which in turn is kept under pressure by the hydraulic pump unit
(C). The pump unit’s motor is activated by one of the pressure switches (5) with
a difference of approx. 10bar. The oil is sucked from the tank through a filter
and compressed via a non-return valve (2) to the accumulator. The safety valve
(1) restricts the pressure to maximum 300bar. The needle valve (3) is used to
release pressure for maintenance purpose and is closed during normal operation.
A hand-operated pump (6) is mounted in parallel to the electrically operated
pump in order to be able to adjust the circuit breaker during maintenance
activities.
2.10.2 ACCUMULATOR
The hydraulic accumulator consists of a
high pressure cylinder in which two chambers are separated from each other by a
floating position. One chamber is filled with high pressure nitrogen (N2) and
the other chamber, which is connected to the hydraulic system, is filled with
oil.
While the hydraulic system is being
pressurized the position is driven by the oil, compressing the gas in the other
chamber. During a switching-on and switching-off cycle, the oil is driven at
great speed by the compressed gas into the drive cylinder. The compressed gas
acts as a gas spring.
The
oil volume in the accumulator is sufficient for the completion of complete
“O-C-O” cycle, or two C-O cycles. A signalling contact (g) is located on the
accumulator to warn of an excessively low gas volume.
2.10.3 HYDRAULIC PUMP
UNIT
The pump unit pressurizes and maintains
that pressure in the hydraulic system, including the accumulator. The hydraulic
pump is driven by an electromotor. The filters necessary to protect the
components from pollutants are located in the pump unit.
The
components mounted on the pump unit include the following:
·
Safety valve. This valve restricts the
pressure in the hydraulic system.
·
A non-return valve in the pressure line
prevents back-flow via the pump when the pump is not operating.
·
A needle valve which act as a by-pass
connection to the tank in order to release pressure during maintenance or
servicing.
·
Oil-fill gap and level gauges for
monitoring the oil level in the tank in the pump unit. The oil level can be
read off the level gauge (approx. 40litres).
·
Pump with electric motor.
·
Hand pump for operating the circuit
breaker during servicing and maintenance
2.10.4 HYDRAULIC SYSTEM
The
three main functions are illustrated in the diagram:
·
Valve block of the drive unit.
·
Hydraulic accumulator.
·
Hydraulic pump unit.
a,b,bl = electromagnetic
valves for “C” and “O”
c, d = servo valves for “C” and “O”
e = bi-stable control valve
f = main cylinder
g = switch for monitoring
h = locking cylinder
1.
Safety valve 6. Hand pump
2.
Non-return valve 7. Test input
3.
2.10.5
ADJUSTMENTS
The hydraulic system operates at a
pressure of 232-282 bar and a no of pressure switches monitor and control the
mechanism. The switches are set at falling pressure, except for “Pump Off”
(A) Setting
level of the pressure switches (±1%)
Switching
diagram of hydraulic pressure monitoring system
·
Pump off
·
Locking tripping operation
·
Falling pressure signal
·
Locking closing operation
·
Pump motor ON
·
Safety pressure
2.11 INTERLOCKING
When
we discuss the interlocking principles, we have to divide the interlocking into
two groups:
·
Safety interlocking;
·
Operational interlocking;
The main difference between both
interlocking is the danger that can occur when a certain interlocking does not
exist. Safety interlocking is necessary to give the operator or autoswitching
equipment no opportunity to create an internal fault in the GIS system or to create
unacceptable operation of equipment. Operational interlocking prevents the
operator for switching the GIS in restricted conditions, sometimes defined by
the customer or electricity board.
An example: High speed earthing switches are designed for
closing on a live circuit, i.e. there will be no safety interlocking to prevent
this. There can be an operational interlocking between a disconnector and a
high speed earth switch, so the earth switch cannot be connected to a live
circuit. Unacceptable operation of equipment can be seen as giving a closing
command.
2.11.1 INTERLOCKING ON
THE GIS EQUIPMENT
The
safety interlocking can be divided into two groups:
·
Equipment related interlocking;
·
Gas & hydraulic related
interlocking.
Most equipment interlocking is related
to the disconnector because this type of switch is not capable of breaking
load, switching is only allowed during equal potential on both sides of the
disconnector. Following equipment related interlocking are examples to prevent
the GIS for an internal fault or unacceptable operation:
·
The disconnector cannot be operated in
intermediate position (intermediate mode disturbance)
·
The disconnectors Q1& Q2 are
mutually interlocked, engaged alternately only.
·
The CB cannot be closed when related
disconnectores are in intermediate position.
·
The disconnectors related to a CB cannot be operated when that
CB is closed
2.11.2 INTERPANEL
INTERLOCKING
In most substation configurations, the interpanel
interlocking is related to two types of interlocking:
·
Inter locking concerning busbar
disconnectors in relation to busbar earthing;
·
Interlocking concerning busbar
disconnectors in relation to the bus
coupler.
2.11.2.1 THE INTERLOCKING BETWEEN BUSBAR DISCONNECTORS
AND BUSBAR EARTHING SWITCHES
Controlling of the busbar disconnectors
of all bays is allowed only when the busbar earthing switch of the related
busbar is open . this interlocking can be provided in two ways:
·
By using a hard contact of the earthing switch
for every bay;
·
By using auxiliary relays per bay and
only one set of hard contacts.
The disadvantage of using 1 hard contact
per bay is the amount of contacts used for this interlocking. For each panel,
one relay per busbar is provided &all these relays are controlled by one
contact of the related busbar earthing switch. Because of the safe operation of
the relay, i.e the relay is energized in a safe situation, a good interlocking
system is provided. The opposite interlocking, interlocking the busbar earthing
switch for closing with the related busbar disconnectors, is done by a series
connection of the auxiliary contacts of all busbar disconnectors.
2.11.2.2 THE
INTERLOCKINGS BETWEEN BUS COUPLER
AND BUSBAR DISCONNECTORS
In a normal situation i.e. when the
buscoupling is not provided, only one busbar disconnector per bay can be
closed. This is to prevent unacceptable busbar coupling. This interlocking is standard
in every bay with two busbar disconnectors. However, when a coupling bay is
situated inside the substation, it is possible
to create equal polarity on both busbar by closing the coupling bay. In
this situation it is allowed to operate both busbar disconnectors of 1 bay.
When both busbar disconnectors of one bay
are closed, it is clear that no opening of the coupling bay is allowed. This
opposite interlocking is also available in each bay. This interlocking is
looped to the buscoupler bay. The mentioned buscoupler related interlocking is
necessary to provide a safe “busbar takeover under load “without a shutdown of
a complete substation.
2.12 NITROGEN N₂
Besides the oil system there is also
nitrogen under high pressure (±280 bar), placed in an accumulator. During
switching of the CB this N₂ will transfer
energy to the oil which now has enough to complete a correct switching
operation. Due to leakage of this gas the situation could occur that there is
not enough N₂ valid to perform a correct switching operation which can
lead to not interrupting the current. To prevent this there
are two security levels;
·
First : Signalling low N₂
(switchgear is still operative)
·
Second : Blocking of electrical
operation (opening as well as closing command)
2.13 CONTROLLING
CIRCUITS OF THE CB
2.13.1 THE PUMPMOTOR
AND ITS HYDRAULIC PRESSURE LEVELS
The
main power circuit normally consists of following components:
·
A MCB (F8) for turning of the main power
·
A motor thermal relay(F7)
·
Auxiliary relay contacts of a hydraulic
switches controlled contactor (K9).
The main switch can be a normal switch or
a micro CB. It is normal engineering practice to place a thermal relay in the
main circuit. Activating of this component will de-energize the control circuit
by contact F7 95/96. Normal operation pressure of the CB is between 272 and
282bar. If the hydraulic pressure drops under a level of 272bar, pressure
switch S16-1 operates. Thus energizing contactor K9.The pump motor tries to
restore the necessary pressure. When the motor is running for more than one
minute, there will be an alarm. This alarm is discussed in a separate unit
about signaling. When the pump motor is restoring the pressure, at 282bar the
pressure switch S17-2 will open, what causes the motor to stop (K9 will de-energize).
Additional to this control circuit, there
are three more metering stages that signal a further dropping pressure. The
first stage (262bar) signals the dropping pressure, a indication that the pump
motor can’t restore the operational pressure. The two other stages block the CB
since passing those stages can’t guarantee a proper operation of the CB. These
two stages are called trip lockout (232BAR) and close lockout (240bar).
2.13.2 ANTI-PUMP
FACILITIES ON THE CB
Another very important item in the CB
controlling is an anti-pump facility in the open K24 4/14 contact in the main
close circuit and the closed K24 3/11 take-over contact in the anti-pumping
circuit: when the CB receives a tripping command, the S1 41/42 contact will
open again when the CB reaches its open end position, thus ending the
anti-pumping facility. The closed K42 3/11 take –over contact prevents the CB
for this failure.
2.13.3 THE TWO TRIPPING
COILS
The CB has one closing coil, controlled
by a anti-pumping facility. The tripping is done by two separate tripping
circuits. Sometimes trip coil supervision is added to this circuit. Hydraulic pressure
low stage 2, nitrogen low or SF6 low stage 2 will cause a locking on the
tripping circuit by de –energizing an auxiliary relay. the two tripping circuit
are included in fig.6
2.14
DISCONNECTORS
Opening a three phase disconnector
provides a safe separation between live circuits and circuits that are switched
off for HV testing.this is created by an earthed construction between HV and
operating personnel. Also a gas separation is provided in the construction of
the disconnector.
2.14.1 SPECIFIC
FEATURES
Automatic earthing of disconnector
conductor is done at open position of disconnector. The disconnector is not a
load breaker, no live circuits can be operated. The driving mechanism is a
servo-motor. substation can remain in service during HV testing.
TECHNICAL
SPECIFICATIONS:
·
Short–time current of disconnector
contacts to earth : 40KA/sec
Rated
current
|
1600A
|
Opening
time
|
4
sec
|
Closing
time
|
4
sec
|
Driving
mechanism
|
Motor
|
Power
supply
|
HVdc
|
2.14.2 AUXILIARY
CONTACTS
The auxiliary contacts in the signaling
box are divided in two groups, the SI
contacts and S2 contacts.
The SI contacts are normally operated
when the disconnector is open. Closing the disconnector will immediately change
the status of SI from operated to not operated. For this reason, the SI contact
is also named “early contact”. The SI contact can be a make or break type, thus
creating early make and early break contacts when the disconnector is closed,
the S2 contacts will become operated. Between changing the status of S1&S2
there is 4sec, for this reason the S2 contacts are named “late make” &
“late break” contacts. The early (A) & late make (B) contacts determine the
end position of the disconnector.
Note;
The switching diagram shows a little time difference between open &close
position of the disconnector and operation of the auxiliary contacts. This is
because the auxiliary contacts have a minimum switching time.
2.15 SWITCHES
One of the components of the L-SEP switchgear
is the three phase earthing switch. The earthing switches are incorporated in
an installation for having the possibility to earth a cable, a line or a busbar
system. The earthing switch is also used for earthing parts of the installation
during tests. In following paragraphs, the specific features and the function
will be described.
2.15.1 SPECIFIC
FEATURES
The earthing switch is of the fault make
type i.e , it is possible to switch on to a live conductor. The insulator
construction of the earthing switch is suitable for a test voltage of 2 KV, which
makes it possible to perform a variety of measurements on the HV termination.
TECHNICAL
SPECIFICATION-
Making
current 65KA
Short-time
current 40KA/sec
Driving
mechanism spring
Operating
mechanism motor
Operating
voltage 110Vdc
2.15.2 AUXILIARY
CONTACTS
The
used auxiliary contacts are operated by a rotating shaft with cams on it.
The S1 contacts are normally operated
when the earthing switch is open. Closing the earthing switch will immediately
change the status of S1 from operated to not operated. For this reason, the S1
contact is also named ”early contact”. The S1 contact can be a make or break
type, thus creating early make& break contacts. When the earthing switch is
closed, the S2 contacts will become operated. Between changing the status of
S1&S2 there is some time. For this reason the S2 contacts are named “late
make”&”late break” contacts. The early break (A)& late make (B)
contacts determine the end position of
the earthing switch.
2.16 SIGNALLING &
ALARMS ON THE LOCAL CONTROL CUBICLE
On
the GIS & its control panel we have several signaling & alarm options.
For example:
·
Position indicators;
·
Auxiliary contacts;
·
Gas density metering;
·
Hydraulic pressure metering;
·
Voltage and/or current metering;
·
Annunciators;
·
Discrepancy signaling lamps.
2.16.1 GAS DENSITY METERING
AND CONTACT BOUNCING
Also blocking and sometimes forced
tripping are controlled by gas density setting. A problem with gas density
metering can be the contact bouncing when a CB is closed or opened. These
actions can cause a nonrealistic alarm when no protection is provided. Our
protection
against
this problem is a time delay on all outgoing gas density alarm signals (3sec).
For blocking circuit no time delay is included because the time delay is only
operative during the switching of the CB.
The gas density alarm also needed a time
delay when they initiate a forced tripping on the CB. By using time delayed
signals, no liquid filled gas density meters have to be used.
2.17 DEFECTS IN GIS
INSULATION
Defects in the insulation system of GIS
may be left from the production of the units in the factory and they are generated
during the assembly at site, or they may occur during normal operation.
Location of the defect is done by searching for the location along GIS with the
highest signal level.
Protrusion on earth and live parts:
A
protrusion from live or earthed parts will create a local field enhancement.
Such defects will have a little influence on AC withstand voltage because
voltage varies slowly, and the corona at the tip will have time to build up a
space charge that shields the tip. For impulses like lightning surge or very
fast transients produced by disconnector operation, the impulse duration is too
short to build such space charge. Consequently the lightning impulse withstand
voltage for instance will be heavily reduced due to this type of flaw .Usually
protrusion exceeding 1-2mm on the phase conductor are considered harmful l. Due
to lower strength a similar protrusion on the encapsulation will be much less
severe.
Free moving or fixed particle:
Free moving particles have little impact
on the LIWL (lightening impulse with stand level),while the AC withstand level
can be significantly reduced by their presence. The reduction will depend on
their shape and position; the longer they are and closer they get to
HV-conducer the more dangerous they become. If they move on to the spacer they
become even more dangerous.
Voids and defects in spacers:
A
defect inside a spacer will give rise to discharges, electric stresses and
eventually lead to breakdown
Electrically and mechanically lose
shields:
Field grading shield becomes
mechanically loose and it may become electrically floating. Floating shield
adjacent to an electrode on potential will give rise to large discharges
between shield electrodes
Benefits using the AIA-1 to detect
and locate flaws in GIS:
Some of the failure in GIS originates
from less suitable designs, but these are continuously being improved. Another
group of failures are considered to be of an almost inevitable stochastic
nature. These are failures initiated by flaws introduced during manufacturing,
assembled at site and during operation. Flashover in a GIS is in general
associated with longer outage times and greater cost than in a conventional air
insulated substation, and their consequences may be severe.
2.17.1THE “HOT
STICK”MEASURING TECHNIQUE:
Measuring on cable terminations is
done with voltage applied during service or as a test after assembly. This
requires a measuring technique tested and approved for live work. For this
purpose a glass fibre rod is used. The sensor of ALA-1 is mounted in the handle
and the acoustic signal is transferred through the glass-fibre stick to the
sensor. The measurements are performed by pressing the tip of the glass fibre
rod onto the laminations at various positions. The tip is equipped with a soft
rubber sphere filled with some sort of grease to obtain good acoustic contact
for the signal. Partial discharges in the termination is discovered when the
100(120) Hz signal is high compared to the 50(60) Hz signal. The plot in
particle mode (amplitude vs elevation time) gives higher amplitudes and shorter
time between discharges as the discharge level increase.
2.18DEMERITS
OF GIS
·
High cost compared to conventional
outdoor substations.
·
Requirements of cleanliness are very
stringent. Dust or moisture can cause internal flashover.
·
Procurement of gas and supply of gas
must be maintained.
·
Project needs almost total imports
including SF6 gas spares.
·
SF6 leakage may lead to suffocation.
Some of the gaseous and solid by –products formed inside G.I.S are hazardous.
2.19 APPLICATIONS OF
GIS
.
Switch gear installations for higher security requirements.
·
Indoor switchgear installations with
minimum space requirements therefore ,specially suitable for congested areas.
·
Protected installations in areas of
contaminations and corrosion by sea or desert climate and in industrial plants.
·
Cavern switch installations for hydro
and pump storage power plants.
·
In power plants, with the possibility of
accommodation in the immediate vicinity of the transformers to achieve an
optimum overall concept.
·
Extension of existing conventional outdoor
installations on a limited ground area.
·
Replacement of existing conventional switchgear
installations enabling increased voltage level, without additional space
requirements
·
SF6 GAS insulated substations (GIS)
·
Hybrid solution as a combination of metal-enclosed
switchgear components together with equipment of conventional design.
·
On hilly terrains.
2.20 POWERLINE CARRIER
COMMUNICATIONS
The 9505 power line carrier (PLC)
terminals supplied by BPL Telecom Ltd are intended for the transmission of speech,
telemetering, teleprinting, telecontrol, teleindication and teleprotection
signals in the carrier frequency range between 50kHz to 500kHz over the following communication
media with suitable line coupling equipments:
High
voltage and medium voltage power lines.
Open
wire lines exposed to power lines.
Message
transmission is based on signal side band (SSB) principle where the carrier
power and one of the two sidebands generated as a result of modulation are
suppressed.
The
advantages of this mode of operations are:
·
Optimum utilization of the available
send power for signal transmission.
- Minimum
channel width to conserve spectrum space.
- Large
transmission range.
The model 9506 PLC provides single or
twin channel voice grade channels for the transmission of speech or audio tones
over HV transmission lines. The 9505 PLC terminals are available in 4
configurations -9505HP,9505IP,9507LP,and 9505SP.The 9505HP configuration
equipped with a 40W amplifier (95AMP-HP)
which feeds the programmable line filter (95PLF-HP) is installed in the GIS .It
utilizes only one channel from the two available.
Coupling mode: The AF coupling mode is
adopted for back coupling of 95PLC terminals .Here he terminals are inter
connected at AF level
2.20.1 OPERATING
PRINCIPLE
9505 PLC consists of the following
sections: AF section, IF/HF section and HF line section. The AF section on the
send side includes input circuit telephony, dial signal generations circuits be
transmitted .These are speech input circuit telephony, dial signal generation
circuits for dialing and pilot signal. On the receiving side, the AF section
has corresponding output circuits which separate out different signals like
speech, dial etc. In order to connect telephone through automatic relay
equipment or PAX, AF hybrid is provided for speech and for 4 wire /2wire
conversion.9505PLC incorporates a speech interface (95PIN) circuit and a data
interface 95(DATA) circuit. The 95MODEM is the heart of the 9505PLC system and
comprises IF/HF section for both transmit and receive side.
The AF signals are converted into IF
signals using the IF carrier of 5.12 MHz generated in the system using a
crystal oscillator .In the transmit section, the IF band is filtered out using
a 10 pole crystal filter and fed to a final mixer stage. The carrier required
for mixing is derived from a voltage controlled oscillator (VCO).The mixer
output is HF signal in the range of 50kHz to 500kHz in steps of 0.5kHz.In the
receiver section, a VCO generates the requires demodulating carrier and IF band
is filtered using a crystal filter. IF to AF demodulation is achieved by using
5.12 MHz as the carrier.
Automatic gain control (AGC) is built unto the
demodulator section regulate AF output for variation in HF input. The HF line
section on the send side has an RF power amplifier to provide high power of
transmission at the terminal output.
2.20.2 FUNTIONAL
DESCRIPTION:
The
9505-HP PLC is provided with the following modules
Power Supply Unit (95PSU-HP):
This provides regulated +/- 12V DC and
unregulated +/- DC outputs .The unregulated outputs are used to power the
output amplifier stages .95PSU-HP is powered by a 48V dc. Voltage regulation
for +/-12V section is achieved through 3 pin regulators. Input over voltage
protection is also provided, the voltage detected by an SCR.
Speech Interface (95sPIN):
This module is the
interface from the speech circuits to the 95MODEM .Interface is provided for
telephone,2 wire express telephone,34 wire express telephone and lack telephone
communications. The jack telephone and 4 wire express telephone act as parallel
channels. This also contains ton – generating circuits for signaling and alarm
indication and speech equalizer.
2.20.3
MODULATOR/DEMODULATOR(95MODEM)
This module contains
two basic sections, a modulator that converts audio signal in to a single side
band (SSB) signal and a demodulator that converts a received SSD signal back into an audio
signal. Both sections use a 5.12MHz interface frequency (IF) signal are
completely independent in their operation. A crystal oscillator in the
demodulator section provides reference frequency for some circuit in the
modulator section.
Modulator section is a single conversion
heterodyning transmitter with an If of 5.12MHz.it produces a double side band
(DSB) signal, which is converted to SSB using filtering techniques. This
modulator section comprises of a synthesizer ,a speech amplifier, a high pass
filter, a compressor/amplifier ,an active low pass filter, a balance modulator
.an IF filter, a mixer, an RF output amplifier, and a signaling transmitter.
The output of speech amplifier is given
to a high pass filter where low frequency components of the speech signal are
limited so as to prevent spurious output near the carrier. An operational
amplifier can configure itself as a signal compressor or amplifier depending on
the ON/OFF signal it receives. If this signal goes low, the OPAMP function as a
compressor and if it goes high it functions as amplifier. Active low pass
filter is used to suppress all speech signal above a specific frequency to
prevent interference with the data channels and signaling tone produced by
signaling transmitter. Balanced modulator accepts signals from active low pass
filter and signaling transmitter. It uses this signal to generate 5.12MHz
signal with DSB s and a suppressed carrier. IF filter suppresses the upper side
band (USB) of balanced modulator output. The demodulator section is a single
conversion receiver that uses the same 5.12MHz IF as in the modulator section
and converts the SSB into audio section .It contains a crystal oscillator, a
synthesizer, an input low pass filter, an input mixer, an IF amplifier, a
product detector, a speech channel low pass filter, an expander/output
amplifier, an FSK band pass filter, a signaling receiver, an audio gain control
circuit and signal to noise ratio alarm,
Crystal oscillator generates reference
frequency for synthesizer in both sections of 95MODEM. Synthesizer set the
frequency at which demodulator section will receive inputs. Input mixer
converts its input signal into 5.12 MHz IF by combining it with the output of
synthesizer and send it to IF amplifier .The output of IF amplifier is fed to
product detector where the signal is combined with 5.12MHz crystal oscillator
output to produce audio output signal. The output of product detector is fed to
audio transformer which splits the signal into two parts. The first part is fed
to OPAMP to produce speech plus output and the other part is fed to input of
speech channel.
CHAPTER 3
CONTROL AND PROTECTION
3.1PROTECTION
Modern power systems
are growing fest with more generators, transformers and large network in the
systems. For system operation a high degree of reliability is required. In
order to protect the system (lines and equipment) a form damage due to undue
current and /or abnormal voltage caused by faults (such as short circuit) the
need for reliable protective devices, such as relays and circuit breakers
arises. The most common electrical hazard against which protection is required
at the short circuit. However there are abnormal conditions – e.g., overloads
under-voltage and over-voltage, open phase, unbalanced phase currents reversal
of power, under-frequency and over-frequency, over-temperature, power swings.
On the occurrence of short circuits which
may lead to heavy disturbances in normal operation damage to equipment,
impermissible drop in voltage etc the protective scheme is designed to
disconnect or isolate the faulty section from the system without any delay. The
protective scheme is designed to energize an alarm or signal whenever the
overload and short circuit do not present a direct danger to the faulted
circuit element and the entire installation .for example, an occurrence of a
single phase fault to earth in overload circuits take the necessary measures
for removal of the abnormality and prevent any interruption in power supply to
consumers.
The main functions of protective
relaying are to detect the presence of faults, their locations and initiate the
action for quick removal from service of any element of power system when it
suffers a short circuit or when it starts to operate in any abnormal manner
that might cause damage or otherwise interface with effective operation of the
rest of the system. The relaying equipment is added in this task by the circuit
breakers that are capable disconnection the faulty element when they are called
upon to do so by the relaying equipment.
3.1.1
OPERATION
OF PROTECTIVE EQUIPMENT
The protective relays
connected in the secondary circuits of current transformers and/or potential
transformers. Under normal operating conditions, the voltage induced in the
secondary of the current transformers is small and therefore current flowing in
the relay operating coil is insufficient in magnitude to close the relay
contacts. This keeps the trip coil of the circuit breaker de-energized.
Consequently the breaker contact remains closed and it carries the normal load
current. On occurrence of fault a large current flows through the primary of
the current transformer. This induces the voltage induces the secondary and
hence the current flowing through the relay operating coil .The relay contact
are closed and trip the coil of the breaker gets energized to open the breaker
contacts .The circuit breaker open its contacts . An arc is drawn between the
contact as they separate. They arc is extinguished at a natural current zero of
the ac wave by suitable medium and technique. After final arc extinction and
final current zero, a high voltage wave appears the circuit breaker contacts
tending to re establish this arc. This comprises a high frequency transient
component superimposed on a power frequency recovery voltage. These phenomena
have a profound influence on the behavior of the circuit breakers and the
associated equipment.
3.2 TYPES OF PROTECTION
In a GIS substation the protection is
much more superior when compared to conventional substation. Mainly the
protection to be provided is of two types namely
·
Feeder protection
·
Transformer protection
The
above can be explained as follows.
3.2.1
FEEDER
PROTECTION
This protection is
given for the different components in the feeder bay. The feeder bay includes
the incoming feeder and outgoing feeder. The different types of feeder
protection are-
·
Backup Protection
a) Over
current protection
b) Earth
fault protection
·
Distance protection
·
Pilot wire protection
3.2.1.1 BACKUP
PROTECTION
Vary frequently ,for
attaining high reliability ,speed up action and improvements in operating
flexibility of the protection scheme, the separate element of a power system
,in addition to main of primary
protection ,are provided with a backup protection . The protection is the first
line of defense and ensures quick-acting and selective clearing of faults
within the boundary of the circuit section of an electrical installation.
Backup protection is the main given to a protection which backs up the main
protection whenever the latter fails in operation, is cut out for repairs etc.
Backup protection is important to the
proper functioning of a good system of electrical protection since percentage
reliability not only of the protective scheme but also of the associated
current transformers, power transformers and circuit breakers cannot be
guaranteed. It is the second line of defense which functions to isolate a
faulty section of the system in case the main protection fails to the following
reasons
·
The dc supply to the tripping circuit
fails
·
The current or voltage supply to the
relay fails
·
The tripping mechanism of circuit
breaker fails
·
The circuit breaker fails to operate
·
The main protective relay fails
Backup
protection consist of two type of protection. They are overcurrent and earth
fault protection.
OVERCURRENT
AND EARTH FAULT PROTECTION
The
general practice is to employ a set of two or three overcurrent relays for
protection against phase-to-phase faults and a separate overcurrent relay for
single line –to-ground faults .Separate earth fault relays are employed because
they can be adjusted to provide faster and more sensitive protection for single
line-to-ground faults that can be provided by the phase relays.
An induction type overcurrent relay
giving inverse time relation with a definite minimum time characteristic is
employed for protection .It consist essentially of an ac energy meter with
mechanism with slight modification to give required characteristics. The relay
has two electromagnets. The upper electromagnet has two winding. One of these
primary and is connected to the secondary of the current transformer in the
line to be protected and is tapped at intervals. The tapings are connected to a
plug setting bridge by which the number of turns in use can be adjusted,
thereby giving the desired current setting. The plug bridge is arranged to
sections of tappings to give over-current range from 10% to 70% or 20 to 80% in
steps of 10% The values assigned to each tap are
expressed in terms of percentage of full-load rating of current transformer with which the relay is associated and
represents and value above which the disc commences to rotate and finally
closes the trip circuit. Thus pick-up current the
rated secondary current transformer multiplied by current setting. Adjustment
of setting is made by inserting a pin between the spring loaded jaw of the
bridge socket at the tap value required. When the pin is withdrawn for the
purpose of changing the setting value while the relay in service, the relay
automatically adopts higher setting, thus the current transformer's secondary
is not open circuited.
The second windings is energized by
induction from the primary, and is connected in series with the winding on the
lower magnet. By this arrangement, leakage fluxes of upper and lower
electro-magnets are sufficiently displaced in space and phase to set up a
rotational torque on the aluminium disc suspended between the two magnets, as
in the shaded pole induction disc motor. This torque is controlled by the
spiral spring and also sometimes by a permanent magnet brake on the disc. The
disc spindle carries a moving contact which bridges two fixed contacts when the
disc has rotated through a pre-set angle. The angle can be set to any value
between 0° and 360° and thereby giving desired time setting. This adjustment is
known as time-setting multiplier. Time multiplier setting is generally in the
form of an adjustable back-stop which decided the arc length through which the
disc travels, by reducing the length of travel, the operating time is reduced.
The time setting multiplier is calibrated from 0 to 1 steps to 0.05.
Each fault current depends on the type
of neutral earthing, i.e., whether solidly earthed, insulated or earthed
through some resistance or reactance. Where no neutral point is available,
grounding transformer is employed. The earth fault current will be small as
compared as phase fault currents in magnitude. The relay thus connected for earth fault protection is
different from the ones provided for phase-to-phase faults.
Here two inverse
definite minimum time type overcurrent relays are connected in two phases
through CT's and one earth-fault relay. In case of phase-to-phase faults or
overload the IDMT relays trip the CB. Under healthy conditions, the sum of all
the three currents of CT's is zero and the earth-fault relay remains inoperative.
As soon as phase-to- changes fault
occurs unbalancing in currents causes the earth- fault relay to operate, which
in turn trip the circuit breaker.
3.2.1.2
DISTANCE PROTECTION
Distance protection is the name given to
the protection, whose action depends upon the distance of the feeding point to
the fault. The time of operation of such a protection is a function of the
ratio of voltage and current i.e., impedance.
Distance relays differ in principle from
other forms of protection in that their performance is not governed by the
magnitude of the current or the voltage in the protected circuit but rather on
the ration of these two quantities. Distance relays are actually double
actuating quantity relays with one coil energized by voltage and the other coil
by current. The current element producers a positive or pick-up torque while
the voltage element producers a negative or rest torque. The relay operates
only when the V/I ratio falls below a predetermined value. During a fault on a
transmission line the fault current increases and the voltage at eh fault point
decreases. The V/I ration is measured at the location of CT's and PT's. The
voltage at FT location depends on the distance between PT and the fault.. If
the fault is nearer, measured voltage is lesser and if the fault is farther,
measured voltage is more. Hence assuming constant fault impedance each value
and the fault along the line. Hence such protection is called the distance
protection or impedance protection.
Distance protection is non- unit type
protection, the protection zone is not exact. The distance protection is high
speed protection and is simply to apply. It can be employed as a primary as
well as back- up protection. It can be employed in carrier aided distance schemes
and
in auto-reclosing schemes. Distance protection is
very commonly used in protection of transmission lines.
Distance relays are
used for both phase fault and ground fault protection and they provide speeds
for cleaning faults than over- current relays. Distance relays are also
independents exchanges in magnitude of the short- circuit currents and hence
they are not much affected by changes in the generation capacity and the
systems configuration. Thus they eliminate long clearing times for fault near
the power sources required by over- current relays if used for the purpose.
Here we use impedance
type distance relay. An impedance relay is a voltage restrained
current relay. The relay measures impedance upto the
point of fault and gives tripping if this impedance is less than the relay
setting impedance. Relay settings impedance is as replica impedance and it is
proportional to the set impedance i.e. impedance upto the reach of the relay.
The relay monitors continuously the line current though current transformer and
the bus voltage through PT and operates when the V/I ratio falls below the set
value.
3.2.1.3
PILOT WIRE PROTECTION
The time "Pilot" means that
between the ends of a transmission line there is an interconnecting channel of some
sort over which information can be conveyed. Three different types of such a
channel are presently in use, and they are called "Wire Pilot"
"Carrier - current pilot" and "Microwave Pilot". The
differential pilot- wire protection is most satisfactory and is widely employed
on account of the advantages such as simplicity, flexibility, a high stability
ratio, and rapid fault clearance.
The differential pilot- wire protection
is based upon the principle that the currents compared at each end of the line
or feeder by the use of pilot wires should be same under normal operating
conditions and the equality is lost only when there is a fault in between the
two ends. The systems is quite similar to that employed for the protection of
alternate and transformers and the difference lies only in the length of pilot
wires.
3.2.2
TRANSFORMER PROTECTION
This
protection is given for different components in the transformer bay. The
different types of transformer protection are
• Over
Current Protection
• Earth
Fault protection
* Different Protection
• Restricted Earth Fault Protection
3.2.2.1
DIFFERENTIAL PROTECTION
Differential protective relaying is the
most positive in selectively and in action. It operates on the principle of
comparison between the phase angle and magnitude of two or more similar
electrical quantities. A differential relay is defined as the relay that
operators when the phasor difference of two or more similar electrical
quantities exceeds a pre-determined amount. This means that for a differential
relay, it should have (i) two or more similar electrical quantities and (ii)
these quantities should have phase displacement for the operation of the relay.
Almost any type of relay, when connected in a certain way, can be made to
operate as a differential relay. Most of the differential relays are of
"Current differential" type in which phasor difference between the
current entering the winding and current leaving the winding is used for sewing
and relay operation.
Differential protection relaying is
generally unit protection. The protected zone is exactly determined by the
location of CT's or PT's. The phasor difference is achieved by suitable
connection of secondaries of CT's or PT's.
3.2.2.2
RESTRICTED EARTH FAULT PROTECTION
Earth fault relays connected in residual
circuit of line CT's provide protection against earth faults on the delta unearthed star- connected windings
of power transformers. A CT is fitted in each connection to the protected and
the secondaries of CT's are connected in parallel to relay. Ideally, the output
of the CT's is proportional to the sum of zero sequence currents in the line
and tae neutral earth connection if the latter is within the protected zone.
For external faults zero sequence currents are either absent or sum to zero in
the line and neutral earth connection. For internal faults, the sum of zero
sequence currents is equals twice the total fault current.
If an earth fault occurs near the
neutral point of the transformer the voltage available for driving earth fault
current is small. For the relay to sense such fault it has to be toe sensitive
and would, therefore operate for spurious signals, extern^ fault current of the
order of 15% of rated winding current.
Such settings restricted portion of the windings. Hence the name restricted
earth-fault protection.
3.3 ADVANTAGES
OF STATIC RELAYS
·
The excellent reliability of
electronic components enables a very good behavior of
protection systems under severe environments. .
·
100% security of operation
even after several years of service without any change in characteristics. .
·
Returning percentage is
equal to / greater than 95%.
·
Accuracy is more than 5% even
in worst case.
·
100 percentage security of
operation even on saturated CT conditions which is
fundamental in over current protection of HV
networks. .
- The cut out area required is only 176th of that of
equivalent electromechanical relays available in India. Hence, more relays can be
accommodated in the same panel.
- The relays are very compact and look elegant.
- Weight and volume is less.
- Operates
faster than conventional electromechanical relays which bring in a real
advantage when complex functions are used. Grading time considerably
reduced.
- Relays will operate satisfactorily within the range of 80-110%
of auxiliary supply voltage.
- Relays have got wide range of settings and are easy to set.
·
Very low burden allowing a
large number of parallel functions on the same CT.
·
Complete passivity to
mechanical and climatic environment.
·
The relays operate trouble
free at ambient temperatures ranging from -5 to +55 degree
centigrade.
·
Secondary of CT's are
automatically shorted on removal of relays from the cases.
·
Relays form rewired modular
protection systems which are l00% factory tested.
3.4 TYPES OF RELAYS EMPLOYED FOR PROTECTION AND CONTROL
3.4.1
THREE PHASE BIASED DIFFERENTIAL
PROTECTION FOR POWER TRANSFORMERS
AND GENERATOR TRANSFORMERS
FEATURES:
- Three
phase biased differential relays for protection of two winding or three
winding transformers.
- No interposing CT's needed. Easy phase angle and current
amplitude compensation by selector switches.
- Percentage characteristics ensure high stability during through
faults.
- Adjustable minimum threshold setting of 20% to 80% IR which
avoids unwanted tripping due
to CT errors, tap changing and magnetizing current when operating off-
load.
- Magnetizing current inrush restraint.
- Over - excitation restraint by desensitization of minimum
threshold.
- Fast operating time
less than 40 milliseconds.
- Indication of faulted phase by Light Emitting Diodes (LED).
- Indication of fault - differential or high-set instantaneous.
- Independent adjustment between the percentage threshold and
minimum threshold.
- Test points on the front face for verifying the connect Tons
and the settings when the equipments
put into service.
- Easy integral test facility to check proper functioning of
the internal circuits of the relay by a test push-button on the front panel.
MODELS
AVAILABLE
Number of windings (2 or
3).
|
Number of phases (1 or
3).
|
APPLICATION
The differential
relay type is designed for the protection of transformers against internal
short circuits, short circuit between phase and short circuit between phase and
earth. It is suitable for the protection of two or three winding power transformers,
auto-transformers or generator transformer units. Generally no interposing
current transformers are needed together with the relay. The phase angle and
current magnitude compensation are carried out with selector switches on the
relay front plate.
DESCRIPTION
The three phase
protection assembly is housed in flush mounted case which is a standard 19”
international rack, of height 196mm, width 482.6mm and depth from the flush
mounting surface is 320mm.The assembly comprises of plug- in cards closed at
the front by an anodized aluminium name and transparent poly–carbonate cover.
The front face consists of-
- One two position switch for current magnitude
compensation
- (1,1//3) per winding
- One two position switch for phase angle(01)
compensation
- (0+120 degree)per winding
- One two position switch for phase angle (02)
compensation (0,+180)per winding
- (Total phase compensation equal to
(01)+(02)+30degree for delta connected internal CT’s and (01)+(02) for
star connected internal CT’s)
- A series of 4mm dia. test terminals for
checking the primary and secondary currents, different current and through
current.
- One switch per winding for transformer ratio
matching on HV and LV sides from 0.6 to 1.26 In steps of 0.06 associated
with a two position switch for the fine adjustments 0,+0.03In.
- Minimum threshold current setting for each
phase from 20% to 00%IR in steps of 20%.
- Percentage slope setting for each phase from
12.5% to 50% in steps of 12.5%
- 3 LED’s with memory for indication of the
faulted phase
- One push button for resetting the LED’s
- One push button per winding to check the
electronics circuit with associated two LED’s per phase to indicate
minimum operating threshold and high set threshold operation.
- The relay case incorporates a terminal block
for external connection with 28 terminations
3.4.2 HIGH IMPEDANCE
OVERCURRENT RELAY
FEATURES
·
Solid state design.
·
Designed for tropical
environment.
·
Self contained relay.
·
Dimensions comply with
international standards.
·
Automatic shorting of C.T.
inputs when modules are withdrawn.
·
Built in test facility.
·
Low burden.
·
High speed of operation.
APPLICATION
TDZA relays
associated with resistors ensures the selective protection of
·
Bus bars against phase to
phase and phase to earth faults.
·
Transformers with an earthed
neutral (restricted earth).
·
MV network against phase to
earth faults.
- Rotating machines.
CONSTRUCTIONAL
FEATURES
The TDZA relay
is housed in a TROPIC PLUS, size 4 case, closed at front by a scalable transparent cover.
Conventional series dropping power supply is employed, and the heat I
generating components in the power supply are mounted in a ventilated metallic
enclosure at the rear side of the case. The
input and output connections are terminated on a terminal block with 28 terminals. The terminal block has CT shorting facility.
Current settings are done by means of movable
plug in jumper. The plug out positions of the jumper corresponds to maximum
setting value. LED indicates operation of relay and can be reset by
"RESET" push button. Built in test facility
is provided to check healthiness of electronic circuits by pressing
"TEST" pushbutton.
GENERAL DESCRIPTION
Relay code:
T -
Tropicalised
D -
Differential operation
Z -
High impedance
A -
Current operated
MODELS AVAILABLE
Description
|
Relay type
|
No of O/P relays
|
Case size
|
Single phase high
impedance overcurrent relay
|
TDZA 10
|
1
|
4
|
Three phase high impedance
overcurrent relay
|
TDZA 30
|
1
|
4
|
When the
fault current exceeds the set value threshold detector generates the output signal
instantaneously. External resistor is used for an excellent stability of the
protection zone.
3.4.3 HIGH SPEED TRIPPING
RELAY TYPE: TMTG
APPLICATION
High speed tripping relay (TMTG) is .used
for those applications where short time is essential for tripping of breakers
in a protective scheme.
MAlN
FEATURES
- High speed of operation.
- Any number of NC or NO or C/0 contacts can be provided as per
customer specification.
- Charter free operation.
- LED Flag indication.
- Electrically hand resettable facility.
- Optional self reset contacts can be provided.
GENERAL
DESCRIPTION
TMTG Relay
basically consists of a miniature attracted armature type relay module with 3
C/0 contacts. This unit is self .held by its own contact and the same is used
to energize an LED indication. The resetting facility is achieved by an N/C
contact push button by operation of which breaks the mains auxiliary supply to
the relay. For additional contacts attracted armature type relay modules with 2
C/0 contacts are used along with the above 3 C/0 relay module. Numbers of
contacts possible are 2, 4 or 6.
NOMENCLATURE
TMTG X !
— — — — > S Self reset.
COIL
RATINGS
Standard coil ratings are given below along with unit consumption.
CASE AND
FINISH
TMTG relay is housed on a tropic plus size 4 case ,closed at fronn
by a selable transparent cover. Conventional series dropping power supply is
employed and heat generating components is the power supply are mounted on a
ventilating metalilic enclosure at the rear side of the case.The input and
output connections are terminated on terminal block wth 28 terminals.
3.4.4 INVERSE TIME
OVERCURRENT OR EARTH FAULT RELAYS
FEATURES
·
Solid state design
·
Designed for tropical
environment.
·
Self contained relay.
·
Automatic shorting of CT
inputs when modules are withdrawn.
·
Built in test facility.
·
Low burden.
·
Wide range of current
settings.
APPLICATION
a) Network
Protection
Inverse time overcurrent relay allows network protection against
overcurrents, short circuits and against fault between phase and earth.
b) Machine Protection
These relays protect alternators and motors against short-circuit
and overloads.
CONSTRUCTIONAL FEATURES
The TSA relay is housed in a TROPIC PLUS,
size 4 or 5 case, closed at front by a sellable transparent cover. Conventional
series dropping power supply is employed, and the heat generating components in
the power supply are mounted in a ventilated metallic enclosure at the
rear-side of the case. The input and output connections are terminated-on
a-terminal block with 28terminals .the terminal block has CT shorting facility.
Current settings (both time delayed (IR)
and instantaneous (ISI) and time setting is done by means of movable plug in
jumpers The plug out positions of these jumpers corresponds to maximum setting
values. High set unit inactive when jumper is in 'oo' position. A fine
adjustment potentiometer is provided for intermediate time setting. LED's
indicate operation of reply and can be reset by 'RESET' push button. Built in
test facility is provided to check Of electronic circuits by
pressing 'TEST' push button.
GENERAL
DISCRIPTION
a)RELAY
CODE
T -
Tropicalised
S - Inverse
characteristics
A - Current
operated
SCHEMATIC
OF TSA311 RELAY
When fault current exceeds the set value the IDMT characteristic
curve is initiated. The output signal is sent to the o/p relay, after the time
delay, as per IDMT curve. Whenever instantaneous feature is employed an
independent threshold detector generates the output signal when fault current
exceeds the set value ( Is ).
3.4.5 HIGH SPEED TRIPPING REPAY TYPE "TMIG"
APPLICATION
High speed
tripping replay (TMIG) is used for those application where short contacting
time is essential for tripping of breakers in a protection scheme.
MAIN
FEATURES
- High speed of operation
- Any number of NU or c/o contacts can be provided as per
customer specification.
- Chatter free operation.
- LED flag indication.
- Electrically hand resettable facility.
- Optional self reset contacts can be provided.
GENERAL
DESCRIPTION
TMIG replay basically consists of
miniature attracted type relay modules with 3 C/O contacts. This unit is self held by its own contact and the
same is used to energize an LED indication. The resetting facility is achieved
by an N/C contact push button by operation of which breaks the mains auxiliary
supply to the relay. For additional contacts attracted armature type replay
modules with 2 C/O contacts are used along with the above 3 C/O relay modules.
Number of contacts possible are 2,4 or 6.
X
|
TMIG --------->S--------> self reset
contacts
COIL
RATINGS
Standard coil ratings
are given below along with unit consumption
CONSUMPTION
|
DE-energized relays surplus per operating relay
|
>D.C
24V 0.7W 2W
30-32V 1W 2W
48V 1.2V 2W
60V 1.5V 2W
110-125V 3.5W 2W
220V 4W 2W
250V 4.5W 2W
|
|
A.C
127-220V 4VA 2VA
220V/380V 4VA 2VA
|
OPERATING
TIME
Less than 12 ms at
rated voltage
Contacts
switching capacity
INSULATION
The relay will withstands a 2.5 KV
a.c rms 50Hz one second between all circuits and the case between all circuits
not intended to be connected together .It will also withstand 1.25KV a.c. rms
50Hz for one second between matching contacts in open position.
CASE AND FINISH
TMIG relay is housed in a TROPIC PLUS size
4 cases, at front by a sealable transparent power. Conventional series dropping
power supply is employed and the heat generating components in the power supply
are mounted a ventilating metallic enclosure at the rear side of the case. The
input and output connections are terminated on a terminal block with 28
terminals
3.4.6 TRIP CIRCUIT
SUPERVISION RELAY, TYPE: TTSG
FEATURES
- Solid state technology.
- Low burden.
- Continuous supervision with breaker open or closed.
- High frequency disturbance & impulse voltage withstands.
APPLICATION
Trip
circuit supervision relay type TTSG provides continuous of the circuit breaker initiating
audible and visual alarms in the event of the failure in the trip circuit or
the mechanism. Supervision is provided for the trip supply, trip circuit
wiring, trip coil and the tripping mechanism of the breaker.
DESCRIPTION
The relay
type TTSG consists of two separate for post-close and pre-close supervision.
Both circuits offer complete supervision as follows. The output replay is
normally energized in a healthy system by drops off:
• If the trip supply is lost or falls below
approximately 80% of the normal voltage.
• If the trip coil or trip circuit wiring is
open circuited.
• In case of failure of circuit breaker
tripping mechanism.
A time
delay of about 400ms on drop-off is built into the circuit to prevent false
operations due to momentary voltage dips caused by faults in other circuits or
during a protection trip. Two pairs of changeover contacts are provided for
initiating audio-visual alarms. An operation indicator with memory is also
provided on the relay. No external current limiting resistors are required. The
relay offers a very high leakage resistance in the trip circuit.
CASE
TTSG relay is housed in a TROPIC PLUS size 4 cases, closed at
front by a scalable transparent cover conventional series dropping power supply
is employed, and the heat generating components in the power supply arc mounted
in a ventilated metallic enclosure at rear side of the case. The input and
output connections are terminated on a terminal block with 28 terminals.
3.4.7 AUXILARY RELAY TYPE ‘TAVG'
APPLICATION
TAVG relays
are generally used wherever contact multiplication are required The main
application of these relays are multiple control and annunciation circuits
where reliability and high speed of operation are essential.
FEATURES
·
High speed of operation.
·
Any number of NC or NO or
C/O contacts can be provided
·
Chatter free operation.
·
LED Flag indication.
·
Electrically hand resettable
facility
·
Optional self reset contacts
can be provided
GENERAL
DESCRIPTION
TVAG relay basically consists of TEC
relay modules with 3 C/O contacts per pole.The resetting facility is achieved
by an NC contact push button which breaks the main auxiliary supply to the
relay.
NOMENCLATURE
E
Hand reset contacts
S
Self reset contacts
|
TAVG
No. of elements (1,2, 3, or 4)
|
COIL
RATINGS
Standard coil ratings
are given below along with unit consumption
CONSUMPTION
|
Range surplus per operating relay
|
>D.C
24V 2W
30-32V 2W
48V
2W
60V
2W
110-125V 2W
220V
2W
250V 2W
|
|
A.C
127-220V 2VA
220V/380V 2VA
|
Relays operate exactly
between 50% and 120% of rated voltage.
OPERATING
TIME
Less than 12 ms at
rated voltage
CONTACT
CAPACITY
OPENING CLOSING
------------------------------------------------------
AC
(220V-50Hz, cos 0.6)
5A 8A
DC (135
Vcc-L/R=30ms)
0.25A 3.5A
-----------------------------------------------------
Continuous
8A
INSULATION
The relay
will withstand 2.5 kv ac r.m.s 50Hz for 1 sec between all circuits and the case
and between all circuits not intended to be connected together. It will also
withstand 1.25kv ac r.m.s 50Hz for 1 sec between matching contacts in open
position.
CASE AND
FINISH
TVAG relay is housed in a TROPIC PLUS size 4 cases, closed at
front by a scalable transparent cover conventional series dropping power supply
is employed, and the heat generating components in the power supply arc mounted
in a ventilated metallic enclosure at rear side of the case. The input and
output connections are terminated on a terminal block with 28 terminals.
* * *
* *
CHAPTER 4
DESIGN OF 110KV GIS
SUBSTATION
4.1
EXISTING ELECTRICAL SYSTEM OF KSEB IN KOLLAM CITY
The power requirements
of Kollam city is provided by four substations namely
(1)
Ayathil
-66kv
(2)
Kavanadu
-110kv
(3)
Kundara
-220kv
(4)
Kottiyam
-110kv
The
electrical section of kollam corporation is divided into eight sections. They
are
(1) Cantonment
(2) Kadappakada
(3) Olai
(4) Thangasseri
(5) Sakthikulangara
(6) Pallimukku
(7) Ayathil
(8) Killikollur
4.2
LOAD ANALYSIS OF KOLLAM CITY IN THE LAST TWO CONSECUTIVE YEARS
The average load taken
by each 11kv on the year 2005&2006 are given below.
PLACE
|
2005
|
2006
|
|
1.
|
HEAD POST OFFICE
|
179.92A
|
187.64A
|
2.
|
KOCHU PILAOAM MOOD
|
188.25A
|
186.54A
|
3.
|
PARVATHI MILL
|
160A
|
166.36A
|
4.
|
POWER HOUSE
|
115A
|
126.27A
|
5.
|
CHINNAKADA
|
169A
|
173.36A
|
6.
|
KADAPPAKADA
|
181A
|
177.1A
|
7.
|
S.N.COLLEGE
|
94A
|
122.18A
|
4.2.1
CONNECTED LOAD STATEMENT OF CONTONMENT SECTION.
Domestic consumers
=8969KW
Commercial light &
fans =3771 KW
Commercial heat &
Small power including 3
HP =8011W
Cinema =2648KW
LT Industrial power
a)
Below 15 KW = 4252KW
b)
B) above 15 KW =1242KW
HT consumers
Above 50KW
=2775KW
Lift Irrigation
a)
Below 15 KW =1000KW
b)
Above 15 KW =447KW
Public water works
LT supply
=121KW
HT supply =6416KW
TOTAL =39652KW
4.2.2
CONNECTED LOAD STATEMENT OF KADAPPAKADA SECTION
.
Domestic consumers =8969KW
Commercial light &
fans =3771 KW
Cinema
=2648KW
LT Industrial power
4.3
DESIGN OF TRANSFORMER
Total connected load
for Cantonment section =39652KW
Total connected load
for Kadappakada section
=21390 KW
Total connected
load =39652 + 21390
=61042 KW
30% of future
expansion =20% of 61042
=73250KW
Total load in KVA =73250/pf
Here we assume pf =0.8
=73250/0.8
=91563KVA
Taking demand
factor =91563/0.8 =114454 KVA
Taking diversity
factor = 114454/2 =57227KVA
= 57.227MVA
=60MVA
So we are taking 3
transformers of capacity 20MVA each.
The rating of the
transformer is 110KV/1kv 20MVA power transformer
4.4
FAULT LEVEL CALCULATION
Assuming base MVA as 100
Base impedance
= (base MVA×100)/(fault MVA)
Choose high value of
fault MVA for design. Therefore take 1124MVA
Base impedance = (100×100)/1124
=8.89%
Total resistance/KM =0.046Ω/KM
Total resistance for
7.2KM cable =7.2×0.046Ω
=0.3312Ω
%line reactance of
7.2KM cable = (line reactance × base MVA)/(KV)²
= (0.3312×100)/ (110)²
=0.0027%
Total % impedance at
110KV =8.89+0.0027
=8.8927%
Fault MVA = (baseMVA×100)/(total
%impedance upto the point)
= (100×100)/8.8927
=1124.52MVA
Fault current at 110KV
bus = (1124.52×10⁶)/
(Г3×110×10³)
= 5.9KA
% Impedance of 110KV,
20 MVA transformer,
% Impedance at base
MVA = (% impedance at
rated MVA ×base MVA)/rated MVA
= (10×10)/20
=50%
Three transformers of
20 MVA are connected in parallel
Total % impedance = 1/z =1/z1 + 1/z2 + 1/z3
1/z =1/50 +1/50
+1/50
=0.06
Z =16.67%
% impedance at 11 KV
bus =8.8927% +16.67%
=25.56%
Fault MVA at 11KV bus
=(base MVA ×100)/(total %impedance upto11KV bus)
= (100×100)/25.56
=391.38
=400MVA
Fault current at 11KV
bus = (400×10⁶)/
(Г3×11×10³)
=20.99KA
≈21KA
4.5
DESIGN OF CABLES AND OVER HEAD LINES
1) FOR
110KV
Rated
current at 110KV side
= (60MVA)/(Г3×110KV)
= (60×10⁶)/(Г3×110×10³)
=314.91A
=315A
Conductor
size = (rated current)/(current density)
Here
we are taking cu conductor
The
current density of cu =1.2A/mm²
Size
of conductor
=315/1.2
=262 sq.mm
So
we are taking 300 sq.mm conductor.
Checking
the size of conductor whether it withstands the fault current
Area
of the conductor =
11.1×Гt ×fault current in KA
=11.1×Г3×5.9
=123.47
mm²
2) FOR
11KV
Rated
current at 11KV side = (20MVA)/
(Г3×11KV)
= (60×10⁶)/
(Г3×11×10³)
=1049.72A
=1050A
Conductor
size =(rated current)/(current density)
Here
we are taking Al conductor
Size
of conductor =1050/0.8 =1312.5sq.mm
So
we are taking 4 runs of 400 sq.mm 3core XLPE cable from the secondary of
transformer to the 11KV distribution pane l. for the 11KV distribution panel
the busbar size is runs of 100mmX10mm CU conductor
4.6
SELECTION OF CIRCUIT BREAKER
A) 110 KV
Rated current =315A
Taking factor of
safety =4
CB rating =252x4
=1260A
Available rating in the
market =1250A
Rating of CB =1250A
Short circuit current
at 110KV side =5.9 KA
=6KA
Considering future
expansion, CB’s are selected such that rated normal current is 1250A and rated
short circuit current breaking current 25KA.
B) 11KV
Rated current =1050A
Taking factor of
safety =2
CB rating =1050X2
=2100A
Available rating in the
market =2500A
Rating of CB
=2500A
Short circuit current
at 11KV side =21 KA
Considering future
expansion, CB’s are selected such that rated normal current is 2500A and rated
short circuit current breaking current 50 KA.
4.7
SELECTION OF CURRENT TRANSFORMER
a) 110 KV
Rated
current
=315A
Available
rating is the market =500A
For
metering and protection we are providing 4 no’s of secondary coils of 1A
Core utilization
|
Core1
|
Core2
|
Core3
|
Core4
|
Main protection
|
Back-up protection
|
Metering
|
Different protection
|
|
burden
|
-
|
30VA
|
||
Minimum knee point
voltage
|
600V
|
600V
|
||
b) 11KV
Rated
current =1050A
Available
rating in the market =1200A
For
metering and protection we are providing 3 no’s of secondary coils of 1A
4.8
SELECTION OF POTENTIAL TRANSFORMER
A) 110KV
1.
Rated voltage -110 ±10%
2.
Rated voltage KV (rms) -123
3.
Rated frequency -50 Hz
4.
System neutral earthing –effectively
earthed
5.
Installation –outdoor
6.
Rated short circuit current KA -25
7.
Rated insulation level
a) Impulse
withstand voltage KV(peak) -450
b) 1
minute power frequency withstand voltage KV (rms) -185
8.
Number of secondary windings -two
9.
Transformer ratio –
110/Г3KV/110/Г3,110/Г3 V
B) 11KV
1. Rated voltage -110 ±10%
2. Rated
voltage kv (rms) -123
3. Rated
frequency -50 Hz
4. System
neutral earthing –effectively earthed
5. Installation
–outdoor
6. Rated
short circuit current KA -25
7. Rated
insulation level
a) Impulse withstand voltage KV (peak)
-75
b) 1 minute power frequency withstand
voltage KV (rms) -38
8. Number
of secondary windings -two
9. Transformer
ratio – 11000/Г3V/110/Г3V,110/Г3 V
4.9
ISOLATORS
TECHNICAL
PARTICULARS
1.
Rated voltage KV(rms) -123
2.
Rated frequency Hz -50Hz
3.
System of neutral earthing –effective
earthed
4.
Type of disconnect –horizontal break
(double)
5.
Number of poles -3
6.
Installation –indoor
7.
Rated normal current amps -1000
8.
Rated short time withstand KA current
-25
9.
Rated duration of short circuit =1sec
10.
Rated peak withstand current KA(peak)
-62.5
11.
Operating mechanism –manual/motorized
–automatic
11KV
distribution feeder, current transformer, circuit breaker, cable
4.10
CT’S FOR 11KV FEEDERS
Rated
secondary current -1049.72A
=1050A
Four
feeders are taken from one transformer.
So
current through one feeder =1050/4 =262.5A
= 263 A
Available
rating for ct in the market is 300A
For
metering and protection we are providing 3 secondary coils
Rating
of CT =300/1-1-1 A
4.11
CB’S FOR 11KV FEEDERS
Rated normal current
=263 A
In each feeder
Taking factor of safety
=4
CB rating =263×4 =1052A
Available rating in the
market =1250A
Short circuit current
at 11KV =21KA
Considering future
expansion CB’s are selected such that rated normal current is 1250 A
And rated short circuit
breaking current is 50KA.
4.12
CABLE FOR 11 KV FEEDERS
Rated normal current
=263 A
In each feeder
Size
of conductor = (rated normal current)/(current density)
Considering economical
aspects we are taking Al as the conductor.
Size of Q conductor =263/0.8 = 328.75 sq.mm
Available size of
conductor is the market is 400sqmm 3 core 11KV XPLE cable
4.13
DESIGNING OF EARTH MAT
40m
40 m
4.13.1
TO CALCULATE THE SIZE OF EARTH CONDUCTOR
For copper brased
joints the formula for area of conductor A = 0.044×i×Гt
A= 0.0044×21000×Г3
A= 160.042 mm sq
Taking 20% allowance
are given to the cross sectional area for a corrosive environment
i.e. A =192.05 mm sq
So we provide 35X 6 mm
sq CU for earth mat which posses an area
of 210 mm sq. hence we propose 35X 6 mm sq CU strips to be buried at 0.5
m below the ground .
Assuming earthmat for a
spacing of 2m, total no; of line =42
Resistivity, ρ =132Ωm
Spacing, D =2m
N= 42
H=0.5m
L=total length of
conductor = (40X42) =1680m
Area =40X40 =1600m sq
Grid resistance Rg =ρ/
(4Xr) + ρ/L -------------(1)
Assuming the earthmat
to be a circle, A =1600m,sq
∏r² =1600m.sq
R =22.57 m
Substituting the value
in eqn (1)
Rg =132/(4X22.57)+132/(16800
=1.54Ω
Inorder to reduce the
resistance below 0.5Ω we provide a chemical named Bromite in the soil.
* * *
* *
CHAPTER 5
COST ANALYSIS
5.1
COST ANALYSIS FOR GIS EQUIPMENTS
Sl.No.
|
Particulars
|
Quantity
|
Unit
|
Rate per unit
|
Amount in crores
|
GIS EQUIPMENT
|
|||||
1.
|
1feeder
+1transformer+1bus coupler
|
2
|
Set
|
5Crore
|
10
|
2.
|
1transformer section
|
1
|
Nos.
|
2crore
|
2
|
3.
|
Metering section
&earthing switch
|
1
|
Nos.
|
4crore
|
4
|
4.
|
110KV,20MVA
transformer
|
3
|
Nos.
|
51,00,000
|
1.5
|
5.
|
Transformer control
&relay panel
|
2
|
Set
|
600000
|
0.12
|
6.
|
11KV distribution
panel with 12 feeders &3bus coupler with relays &metering
|
1
|
Set
|
50,00,000
|
0.5
|
7.
|
Station battery
|
0.015
|
|||
8.
|
Rectifier arrangement
|
0.005
|
|||
9.
|
300mm2110KV straight
joint
|
06
|
Nos.
|
15000
|
0.009
|
10.
|
415V LT panel for
substation
|
01
|
Nos.
|
2,00,000
|
0.02
|
11.
|
Earthing material
copper 50*6 sq mm
Including all
equipment earthing
|
10
|
Tonnes
|
500000/ton
|
0.5
|
12.
|
11kv ,3C *300Sqmm
cable (11KV distribution panel to RMU)
|
300
|
Metre
|
5000/m
|
0.15
|
13.
|
RMU
|
12
|
Nos.
|
5,50,000
|
0.66
|
14.
|
3core*400sq mm 110KVXLPE cable (transformer to 11kv
distribution panel )
|
120
|
Metre
|
30000/m
|
0.36
|
15.
|
Auxiliary transformer
200KVA outdoor oil cooled
|
1
|
Nos.
|
1,60,000
|
0.016
|
16.
|
1C*300sq mm 110KV X
LPE cable /copper conductor with adequate insulation angle iron trace
supports, brackets
|
60
|
Metre
|
5000.00
|
0.03
|
17.
|
Cable glands, cable crimping
sockets etc
|
Lumpsum
|
0.03
|
Labour charges @ 10% =1.94 crore
Contingency charges @
10% =1.94 crore
Transportation charges
@ 55 =0.97 crore
Cost
for GIS equipment =24.25 crore
5.2
COST ANALYSIS OF FEEDER BAY- KAVANAD
SL.NO
|
Particulars
|
Quantity
|
Unit
|
Rate per unit
|
Amount in crores
|
1.
|
110kv lighting
arrester
|
6
|
Nos.
|
42,000
|
0.025
|
2.
|
110kvsf6 circuit
breaker
|
1
|
4,50,000
|
0.045
|
|
3.
|
110kvbus isolator
|
3
|
Nos.
|
61,000
|
0.018
|
4.
|
110kvline isolator
|
6
|
Nos.
|
72,000
|
0.0432
|
5.
|
110kv CT
|
3
|
Nos.
|
71,000
|
0.0213
|
6.
|
110kv PT
|
3
|
Nos.
|
72,000
|
0.0216
|
7.
|
Feeder control/ relay
panel
|
4,00,000
|
0.04
|
||
8.
|
Control cable
|
Lumpsum
|
3,50,000
|
0.035
|
|
9.
|
300mm2 XLPE 3 core UG
cable
|
7.2
|
Km
|
8,13,000/km
|
0.5853
|
10.
|
300mm2 ACSR conductor
for bus extension and for feeder bay
|
60
|
15000.00
|
0.09crore
|
|
11.
|
Supporting angle iron
for line erection
|
20
|
20,000/tonne
|
0.04
|
|
12.
|
Suspension isolator’s
suitable for 110KV
|
3
|
30,000/set
|
0.009
|
|
13.
|
Cable trench cable
laying
|
Lumpsum
|
2,00,000.00
|
0.02
|
|
14.
|
110KV ,300sq mm
straight jointing kit
|
3
|
Nos.
|
15,000
|
0.045
|
15.
|
PLCC cable for
carrier communication
|
7.2
|
Km
|
50,000.00/km
|
0.036
|
16.
|
Cable duct
|
7.2
|
Km
|
2,50,000.00/km
|
0.18
|
17.
|
Angle iron support on
the cable duct
|
2
|
Tonne
|
20000/ton
|
0.004
|
18.
|
Earthing material GI
strips
|
3
|
Tonne
|
200000
|
0.06
|
19.
|
Nuts, bolts, washers
etc
|
Lumpsum
|
25,000
|
0.0025
|
|
Total = 1.2809 crores
Labour charges @ 10% =1.94 crore
Contingency
charges @ 10% =1.94 crore
Transportation
charges @ 5% =0.97 crore
Cost
for constructing feeder in Kavanadu
S/S =1.601 crore
5.3
COST ANALYSIS (FEEDER SUPPLY )
---AYATHIL S/S
|
|||||
SL.NO
|
Particulars Quantity Unit Rate per unit Amount in crores
|
||||
1.
|
110kv lighting
arrester
|
6
|
Nos.
|
||
2.
|
110kvsf6 circuit
breaker
|
1
|
|||
3.
|
110kvbus isolator
|
3
|
Nos.
|
||
4.
|
110kvline isolator
|
6
|
Nos.
|
||
5.
|
110kv CT
|
3
|
Nos.
|
||
6.
|
110kv PT
|
3
|
Nos.
|
||
7.
|
Feeder control/ relay
panel
|
||||
8.
|
Control cable
|
Lumpsum
|
|||
9.
|
300mm2 XLPE 3 core UG
cable
|
7.2
|
Km
|
||
10.
|
300mm2 ACSR conductor
for bus extension and for feeder bay
|
60
|
|||
11.
|
Supporting angle iron
for line erection
|
20
|
|||
12.
|
Suspension isolator’s
suitable for 110KV
|
3
|
|||
13.
|
Cable trench cable
laying
|
Lumpsum
|
|||
14.
|
110KV ,300sq mm
straight jointing kit
|
3
|
Nos.
|
||
15.
|
PLCC cable for
carrier communication
|
7.2
|
Km
|
15,000
|
|
16.
|
Cable duct
|
7.2
|
Km
|
2,50,000.00/km
|
|
17.
|
Angle iron support on
the cable duct
|
2
|
Tonne
|
20000/ton
|
|
18.
|
Earthing material GI
strips
|
3
|
Tonne
|
200000
|
|
19.
|
Nuts,bolts,washers
etc
|
Lumpsum
|
25,000
|
5.4
COST ANALYSIS OF GIS BUILDING
SL.NO
|
DESCRIPTION
|
quantity
|
unit
|
Rate per unit
|
Amount in crores
|
1.
|
Building construction
cost of three storied RCC building (30m*26m*12M)
|
2340
|
Sq.mm
|
2100.00
|
0.4914
|
2.
|
M>S structure for
cranes supporting frames for equipments
|
4000
|
Kg
|
60.00
|
0.024
|
3.
|
Motorized crane (20
ton capacity)
|
1
|
no
|
8,00,000.00
|
0.08
|
4.
|
Electrification of
the building
|
LS
|
2,50,000.00
|
0.02
|
|
5.
|
Sanitation
&plumping
|
LS
|
1,50,000.00
|
0.015
|
|
6.
|
Demolishing of
existing quarters
|
LS
|
50,000.00
|
0.005
|
|
7.
|
Developing of
substation yard
|
LS
|
1,00,000.00
|
0.01
|
Total =0.6454 crore
5.5
TOTAL COST FOR ENTIRE PROJECT
COST ANALYSIS =GIS
EQUIPMENTS AND OUTGOING FEEDERS =24.25 crore
COST ANALYSI S (FEEDER
SUPPLY)- KAVANAD S/S =1.601 Crore
COST ANALYSIS (FEEDER
SUPPLY) -AYATHIL S/S =1.02 Crore
COST ANALYSIS OF GIS
BUILDING =0.6454 crore
GRAND TOTAL=27.52 Crores
CHAPTER 6
ADVANCED CONTROL SYSTEM
6.1
INTRODUCTION
An advanced control system is being
proposed for the 110KV substation. In this advanced control system, whole of
the substation components are modeled using simulink in MATLAB software. MATLAB
is a software introduced by a company known as ‘Math Works. Inc.” which is used for mathematical operations. This
software is basically a modeling software and any equipment can be modeled
using this software. Then the model is
simulated by pressing “ Start Simulation” button. Afterwards we can view the characteristics
at any part of the system by viewing the scope. Basically three main equipments
are needed to interface the incoming busbar voltage with the computer. The
three main equipments are-
·
Voltage Transducer
·
Microcontroller
·
Parallel Port Programmer
The incoming busbar
voltage is fed to the voltage transducer. Since the output of the voltage
tansducer is analog in nature and the input to the microcontroller must be
digital in nature, an Analog to Digital converter must be placed in between the
voltage transducer and microcontroller to interface them. The output of the
microcontroller is fed to the parallel port programmer. The last stage includes
the connection of parallel port programmer and computer.
6.2 VOLTAGE TRANSDUCER
Voltage Transducer measures AC Voltage
and converts it to an industry standard output signal which is directly
proportional to the measured input. These Transducers provide an output which
is load independent and isolated from the input. The output can be connected to
Controllers, Data-Loggers, PLC's, Analog / Digital Indicators, Recorders for
display, analysis or control. They are ideal for SCADA, Energy Management,
Telemetering for Remote, Local as well as Central Monitoring Systems.
VMT, VMT – TRMS
BPVMT, BPVMT – TRMS
6.3
MICROCONTROLLER
A microcontroller (also microcomputer,
MCU or µC) is a small computer on a single integrated circuit consisting
internally of a relatively simple CPU, clock, timers, I/O ports, and memory.
Program memory in the form of NOR flash or OTP ROM is also often included on
chip, as well as a typically small amount of RAM. Microcontrollers are designed
for small or dedicated applications. Thus, in contrast to the microprocessors
used in personal computers and other high-performance or general purpose
applications, simplicity is emphasized. Some microcontrollers may use four-bit
words and operate at clock rate frequencies as low as 4 kHz, as this is
adequate for many typical applications, enabling low power consumption
(milliwatts or microwatts). They will generally have the ability to retain
functionality while waiting for an event such as a button press or other
interrupt; power consumption while sleeping (CPU clock and most peripherals
off) may be just nanowatts, making many of them well suited for long lasting
battery applications. Other microcontrollers may serve performance-critical
roles, where they may need to act more like a digital signal processor (DSP),
with higher clock speeds and power consumption.
Microcontrollers
are used in automatically controlled products and devices, such as automobile
engine control systems, implantable medical devices, remote controls, office machines,
appliances, power tools, and toys. By reducing the size and cost compared to a
design that uses a separate microprocessor, memory, and input/output devices,
microcontrollers make it economical to digitally control even more devices and
processes. Mixed signal microcontrollers are common, integrating analog
components needed to control non-digital electronic systems.
6.3.1
DETAILS OF ATMEGA 32
FEATURES
• High-performance, Low-power AVR® 8-bit Microcontroller
• Advanced RISC Architecture
– 131 Powerful Instructions – Most Single-clock Cycle Execution
– 32 x 8 General Purpose Working Registers
– Fully Static Operation
– Up to 16 MIPS Throughput at 16 MHz
– On-chip 2-cycle Multiplier
• Nonvolatile Program and Data Memories
– 32K Bytes of In-System Self-Programmable Flash
Endurance: 10,000 Write/Erase
Cycles
– Optional Boot Code Section with Independent Lock Bits
In-System Programming by On-chip
Boot Program
True Read-While-Write Operation
– 1024 Bytes EEPROM
Endurance: 100,000 Write/Erase
Cycles
– 2K Byte Internal SRAM
– Programming Lock for Software Security
• JTAG (IEEE std. 1149.1 Compliant) Interface
– Boundary-scan Capabilities According to the JTAG Standard
– Extensive On-chip Debug Support
– Programming of Flash, EEPROM, Fuses, and Lock Bits through the JTAG
Interface
• Peripheral Features
– Two 8-bit Timer/Counters with Separate Prescalers and Compare Modes
– One 16-bit Timer/Counter with Separate Prescaler, Compare Mode, and
Capture Mode
– Real Time Counter with Separate Oscillator
– Four PWM Channels
– 8-channel, 10-bit ADC
8 Single-ended Channels
7 Differential Channels in TQFP
Package Only
2 Differential Channels with
Programmable Gain at 1x, 10x, or 200x
– Byte-oriented Two-wire Serial Interface
– Programmable Serial USART
– Master/Slave SPI Serial Interface
– Programmable Watchdog Timer with Separate On-chip Oscillator
– On-chip Analog Comparator
• Special Microcontroller Features
– Power-on Reset and Programmable Brown-out Detection
– Internal Calibrated RC Oscillator
– External and Internal Interrupt Sources
– Six Sleep Modes: Idle, ADC Noise Reduction, Power-save, Power-down,
Standby
and Extended Standby
• I/O and Packages
– 32 Programmable I/O Lines
– 40-pin PDIP, 44-lead TQFP, and 44-pad MLF
• Operating Voltages
– 2.7 - 5.5V for ATmega32L
– 4.5 - 5.5V for ATmega32
• Speed Grades
– 0 - 8 MHz for ATmega32L
– 0 - 16 MHz for ATmega32
• Power Consumption at 1 MHz, 3V, 25°C for ATmega32L
– Active: 1.1 mA
– Idle Mode: 0.35 mA
– Power-down Mode: < 1 μA
6.3.2
OVERVIEW
The ATmega32 is a
low-power CMOS 8-bit microcontroller based on the AVR enhanced RISC
architecture. By executing powerful instructions in a single clock cycle, the ATmega32
achieves throughputs approaching 1 MIPS per MHz allowing the system designer to
optimize power consumption versus processing speed.
The AVR core combines a rich
instruction set with 32 general purpose working registers. All the 32 registers
are directly connected to the Arithmetic Logic Unit (ALU), allowing two independent
registers to be accessed in one single instruction executed in one clock cycle.
The resulting architecture is more code efficient while achieving throughputs
up to ten times faster than conventional CISC microcontrollers.
The ATmega32 provides the following
features: 32K bytes of In-System Programmable Flash Program memory with
Read-While-Write capabilities, 1024 bytes EEPROM, 2K byte SRAM, 32 general
purpose I/O lines, 32 general purpose working registers, a JTAG interface for
Boundary-scan, On-chip Debugging support and programming, three flexible
Timer/Counters with compare modes, Internal and External Interrupts, a serial programmable
USART, a byte oriented Two-wire Serial Interface, an 8-channel, 10-bit ADC with
optional differential input stage with programmable gain (TQFP package only), a
programmable Watchdog Timer with Internal Oscillator, an SPI serial port, and
six software selectable power saving modes.
The Idle mode stops the CPU while
allowing the USART, Two-wire interface, A/D Converter, SRAM, Timer/Counters,
SPI port, and interrupt system to continue functioning. The Power-down mode
saves the register contents but freezes the Oscillator, disabling all other
chip functions until the next External Interrupt or Hardware Reset. In
Power-save mode, the Asynchronous Timer continues to run, allowing the user to
maintain a timer base while the rest of the device is sleeping. The ADC Noise
Reduction mode stops the CPU and all I/O modules except Asynchronous Timer and
ADC, to minimize switching noise during ADC conversions. In Standby mode, the
crystal/resonator Oscillator is running while the rest of the device is
sleeping. This allows very fast start-up combined with low-power consumption.
In Extended Standby mode, both the main Oscillator and the Asynchronous Timer
continue to run.
The device is manufactured using Atmel’s
high density nonvolatile memory technology. The On-chip ISP Flash allows the
program memory to be reprogrammed in-system through an SPI serial interface, by
a conventional nonvolatile memory programmer, or by an On-chip Boot program
running on the AVR core. The boot program can use any interface to download the
application program in the Application Flash memory. Software in the Boot Flash
section will continue to run while the Application Flash section is updated,
providing true Read-While-Write operation. By combining an 8-bit RISC CPU with
In-System Self-Programmable Flash on a monolithic chip, the Atmel ATmega32 is a
powerful microcontroller that provides a highly-flexible and cost-effective
solution to many embedded control applications.
The ATmega32 AVR is supported with a full
suite of program and system development tools including: C compilers, macro
assemblers, program debugger/simulators, in-circuit emulators, and evaluation
kits.
6.3.3
PIN DESCRIPTIONS
Pin
Configurations
Figure 1. Pinouts of ATmega32
VCC- Digital
supply voltage.
GND- Ground.
Port
A (PA7..PA0)- Port A serves as the
analog inputs to the A/D Converter. Port A also serves as an 8-bit
bi-directional I/O port, if the A/D Converter is not used. Port pins can
provide internal pull-up resistors (selected for each bit). The Port A output buffers
have symmetrical drive characteristics with both high sink and source
capability. When pins PA0 to PA7 are used as inputs and are externally pulled
low, they will source current if the internal pull-up resistors are activated.
The Port A pins are tri-stated when a reset condition becomes active, even if
the clock is not running.
Port
B (PB7..PB0)- Port B is an 8-bit
bi-directional I/O port with internal pull-up resistors (selected for each bit).
The Port B output buffers have symmetrical drive characteristics with both high
sink and source capability. As inputs, Port B pins that are externally pulled
low will source current if the pull-up resistors are activated. The Port B pins
are tri-stated when a reset condition becomes active, even if the clock is not
running. Port B also serves the functions of various special features of the
ATmega32.
Port
C (PC7..PC0)- Port C is an 8-bit
bi-directional I/O port with internal pull-up resistors (selected for each bit).
The Port C output buffers have symmetrical drive characteristics with both high
sink and source capability. As inputs, Port C pins that are externally pulled
low will source current if the pull-up resistors are activated. The Port C pins
are tri-stated when a reset condition becomes active, even if the clock is not
running. If the JTAG interface is enabled, the pull-up resistors on pins
PC5(TDI), PC3(TMS) and PC2(TCK) will be activated even if a reset occurs. The
TD0 pin is tri-stated unless TAP states that shift out data are entered. Port C
also serves the functions of the JTAG interface and other special features of
theATmega32.
Port
D (PD7..PD0)- Port D is an 8-bit
bi-directional I/O port with internal pull-up resistors (selected for each bit).
The Port D output buffers have symmetrical drive characteristics with both high
sink and source capability. As inputs, Port D pins that are externally pulled
low will source current if the pull-up resistors are activated. The Port D pins
are tri-stated when a reset condition becomes active, even if the clock is not
running. Port D also serves the functions of various special features of the
ATmega32.
RESET- Reset
Input. A low level on this pin for longer than the minimum pulse length will
generate a reset, even if the clock is not running. The minimum pulse length is
given in data table. Shorter pulses are not guaranteed to generate a reset.
XTAL1- Input to the inverting
Oscillator amplifier and input to the internal clock operating circuit.
XTAL2- Output from the
inverting Oscillator amplifier.
AVCC- AVCC
is the supply voltage pin for Port A and the A/D Converter. It should be
externally connected to VCC, even if the ADC is not used. If the ADC is used,
it should be connected to VCC through a low-pass filter.
AREF- AREF
is the analog reference pin for the A/D Converter.
6.4 PARALLEL PORT
PROGRAMMER
6.4.1
GENERAL TYPES OF DIGITAL DATA COMMUNICATION
1.
Parallel
- Serial
Parallel
Parallel
communication requires as much wires as the no. of bits in a word for its
transmission. Word may be a combination of 4, 8, 16, 32 or 64 bits etc.
Serial
Serial
communication usually requires a minimum of 2 wires for data transmission in
one direction. One wire is for data and other is for ground.
Parallel
port identification on IBM PC
Usually ports are found on the rear of
computer and are of the following two
types;
1) Male
ports - having pins coming out of port.
2) Female ports
- having holes for pins.
Parallel
port is generally a 25 pin female connector with which a printer is usually
attached.
Grouping
Of Parallel Port Pins
i.
Data port
ii.
Status port
iii.
Control port
Data
port:
•
It includes pin 2 to pin 9 with pin
names Data-0 to Data- 9
•
It is usually for data output according
to old “standard parallel port” standard.
ii.
Status Port
Status
port is an input only port i.e. Data can’t be output on this port but it can
only be read.
iii.
Control port
Control
port is a read / write port. For printer purposes it is write only port
6.5 PARALLEL PORT
PROGRAMMER FOR ATMEGA 16/32
In-system programmer
means we can design a programmer circuit using simple parallel port interfacing
such that our controller can be directly burned with the program while in the
designed system or circuit board.
Following
pins of Atmega16 is used in programmer circuit-
Pin No.
|
Description
|
6
|
MOSI (SPI Bus Master Output/Slave Input
|
7
|
MISO (SPI Bus Master Input/Slave Output)
|
8
|
SCK (SPI Bus Serial Clock)
|
9
|
Reset
|
10
|
Vcc
|
11
|
Ground
|
Table-Atmega16 Pins
• SCK – Port B, Pin 7
SCK: Master Clock
output, Slave Clock input pin for SPI channel. When the SPI is enabled as a
Slave, this pin is configured as an input regardless of the setting of
DDB7.When the SPI is enabled as a Master; the data direction of this pin is
controlled by DDB7. When the pin is forced by the SPI to be an input, the
pull-up can still be controlled by the PORTB7 bit.
• MISO – Port B, Pin 6
MISO: Master Data
input, Slave Data output pin for SPI channel. When the SPI is enabled as a
Master, this pin is configured as an input regardless of the setting of DDB6.
When the SPI is enabled as a Slave, the data direction of this pin is
controlled by DDB6. When the pin is forced by the SPI to be an input, the
pull-up can still be controlled by the PORTB6 bit.
• MOSI – Port B, Pin 5
MOSI: SPI Master Data
output, Slave Data input for SPI channel. When the SPI is enabled as a Slave,
this pin is configured as an input regardless of the setting of DDB5. When the
SPI is enabled as a Master, the data direction of this pin is controlled by DDB5.
When the pin is forced by the SPI to be an input, the pull-up can still be
controlled by the PORTB5 bit.
• RESET-Pin 9
Reset Input. A low level on this pin for
longer than the minimum pulse length will generate a reset, even if the clock
is not running.
• VCC -Pin 10
Digital supply voltage(+5V).
•GND-Pin-11 Ground.
Parallel Port-
Parallel Port
interfacing is the simplest method of interfacing. Parallel Port’s are
standardized under the IEEE 1284 standard first released in 1994. It has data transfer
speed up to 1Mbytes/sec. Parallel port is basically the 25 pin Female connector
(DB-25) in the back side of the computer (Printer Port). It has 17 input lines
for input port and 12 pins for output port. Out of the 25 pins most pins are
Ground and there is data register (8 bit), control register (4 bit) and status
register (5 bit).
Following Pins are used in parallel port-
Pin No.
|
Description
|
7,8,9
|
Data pins
|
10
|
Status pin
|
19
|
Ground
|
Table- Parallel Port
Pins
Interfacing -
In programmer circuit
pins of parallel port which are above described has to interface with pins of
ATmega16 microcontroller which are responsible for in-system programming. The
parallel port can be interfaced directly with microcontroller. To avoid reverse
current we can use Schottkey diodes as safety precaution for pc motherboard.
Following pins of
Parallel Port and ATmega16 are to be interfaced-
Parallel Port
|
Atmega16
|
Pin 7
|
Reset (Pin 9)
|
Pin 8
|
SCK (Pin8)
|
Pin 9
|
MOSI (Pin6)
|
Pin 10
|
MISO(Pin7)
|
Pin 19
|
Ground(Pin11)
|
Interface Connections-
Fig-Circuit Diagram
of ATmega16 Programmer
Fig. The Snapshot
SOFTWARES USED:
WinAVR– WinAVR is open source
package in which we use two sub-programs
Programmers,
Notepad & Mfile.
Version- 2.0.8.718-basic
Creator- Simon
Steele
Purpose- 1.
To write code.
2. To compile coding.
3. To generate Hex Code.
4. To burn Hex code.
6.6 MATLAB MODELS AND SCOPE OUTPUT
As a demo for our proposal, we are including
the MATLAB models and scope outputs of three relays namely-
·
Instantaneous relay
·
Differential relay
·
Overcurrent relay
INSTANTANEOUS RELAY
MODEL
SCOPE
OUTPUT OF INSTANTANEOUS RELAY
DIFFERENTIAL
RELAY MODEL
SCOPE
OUTPUT OF DIFFERENTIAL RELAY
OVERCURRENT RELAY MODEL
SCOPE
OUTPUT OF OVERCURRENT RELAY
* *
* * *
CHAPTER 7
CONCLUSION
From the review of conventional
substation the large size & inadequacy in the safety factor was noted. Thus,
the need of a compact and safe working environment came up. The properties of
SF6 was studied and this lead to the design of a 110KV GIs substation for Kollam
city with SF6 as an effective insulating medium. The cost analysis is also
carried out. We have also proposed a advanced control system for the substation
using MATLAB software which enables highly technical as well as easy monitoring
of the operations occurring in the substation.
Certain things to be taken care are that
proper steps should be taken in the design and maintenance of the substation
equipments, else it may affect the satisfactory functioning of the substation.
Space savings, the most significant benefit of GIS substation should be
evaluated not only in terms of locating the substation where it benefits the
electrical system but also provides other financial oppurtunities or avoid
controversy and delays.
REFERENCES
1.
LEEDS W.M.FRIEDDRICH R.E,WAGNER
C.L.HT.CB with Sf6(report of
international conference about high voltage ,1960
2.
BROWN T.E, LEEDS W.M –A new extinction
agent for breaking devices (report of international conference about HV,1960)
3.
MOHANA RAO.M, NAIDU M.S –very fast
transient voltage and transient
enclosure voltage in a GIS
substation (ELECTRICAL INDIA,15th April 1997)
4.
PHIL BOLIN –Engineers note book
(ELECTRICAL WORLD March/April 2000)
5.
www.toshiba.com
6.
www.aba.com
7.
British Library Direct: A technical design 110KV GIS substation
8. www.jacobsbabtie.com/
Free classifieds in Hyderabad
ReplyDeleteFree classifieds in Chennai
Free classifieds in Bangalore
Free classifieds in Mumbai
Free classifieds in ahmedabad
Free classifieds in India
<a href="http://www.Kollam.zazspot.com>Free classifieds in Kollam</a>
Impressive and informative post shared. It is really helpful!!
ReplyDeleteTransformer Manufacturer in India
With RentalCars you can find the cheapest car hires at over 49000 locations globally.
ReplyDeletegood info and thanks for sharing it we are supplying good quality of product Control Relay Panels in Hyderabad
ReplyDelete